2004-06-19 00:00:00 | PLAN REVIEW DENIED, FBC 2001 FUEL GAS |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| (2)104.6.5 BUILDING PERMIT VALUATION. |
| IN THE OPINION OF THE BUILDING OFFICIAL |
| THE CLAIMED VALUATION OF BUILDING, AL- |
| TERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED ESTIMATES |
| AND/OR BONA FIDED SIGNED CONTRACTS (EX- |
| CLUDING LAND VALUE) TO MEET THE APPROVAL |
| OF THE BUILDING OFFICIAL. FOR PERMITTING |
| PURPOSES, VALUATION FOR BUILDINGS AND |
| SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| SWIFT OR THE SOUTHERN BUILDING CODE |
| CONGRESS INTERNATIONAL VALUATION TABLES, |
| LATEST EDITION, AND SHALL BE BASED ON |
| TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- |
| ICAL, INTERIOR FINISH, NORMAL SITE WORK |
| (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| ARCHITECTURAL AND DESIGN FEES, OVERHEAD |
| AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| (3) BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| (4) SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| END OF COMMENTS, QUESTIONS 561-805-6692 |