Plan Review Notes For Permit 04060201 |
Permit Number |
04060201 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-07 00:00:00 | ***************DENIED******************* | | 1) HOW WILL THE FIRE SPRINKLER COVERAGE | | BE EFFECTED BY THE INTERIOR REMODEL. | | | | 2) THE INTERIOR FINISH CLASSIFICATION | | FOR WALLS AND CEILINGS SHALL BE EITHER | | CLASS "A","B" OR "C". | | | | 3) SEPARATE PLANS AND PERMIT APPLICATION | | ARE REQUIRED FOR FIRE SPRINKLER REMODEL. | | | | NATE MCCRAY, CAPTAIN | | 835-2910 OR 805-6722 |
|