Plan Review Notes For Permit 04060201 |
Permit Number |
04060201 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-23 00:00:00 | BUILDING PLAN REVIEW | | PERMIT:04060201 | | ADD:201 S. NARCISSUS AV #403 | | CONT:PAUL NEWMAN | | TEL: (561)719-4248 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | 2) SHEET A.O IN YOUR NOTES STATES TYPE | | OF BLDG. AS TYPE III. PLEASE SEE FBC | | SEC.311.2 | | | | 3) NOTO: FAIR HOUSING ANSI A117 CHANGES | | OF FLOOR LEVELS SEE SEC. 303.3 WHICH IS | | 1/4" ALLOWED. SEE SEC.303.4 BEVELS USED | | ON THRESHOLDS MAX HEIGHT IS 1/2". | | | | | | 4) FLOOR: THE THICKNESS OF PLYWOOD SEE | | FBC CH 8 SEC.803.7.2. TYPE II | | CONSTRUCTION INSULATING BOARD SHOULD NOT | | BE MORE THAN 1/2" | | | | ) PLEASE SUBMIT ADDITIONAL DETAILS | | TO SHOW ATTATCHMENT AND FASTENING OF | | MATERIALS TO FLOOR AND CEILING DECK. | | | | 6) SUBMIT TYPE OF BACKING TO BE USED IN | | ALL WALLS. SEE SHEET A.8 DETAIL#3 | | 609.2.1 FIRE RETARDENT TREATED WOOD. | | | | | | 7) TABLE 803.3 MINIMUM INTERIOR FINISH | | CLASSIFICATION; PROVIDE INFORMATION | | BASED ON INTERIOR FINISH REQUIREMENTS | | BASED ON OCCUPANCY. ALSO SEE SEC.803.4 | | | | | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | MYRON JACOBS | | TEL: (561)805-6726 | | FAX: (561)659-8026 |
|