2004-06-23 00:00:00BUILDING PLAN REVIEW
 PERMIT:04060201
 ADD:201 S. NARCISSUS AV #403
 CONT:PAUL NEWMAN
 TEL: (561)719-4248
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET A.O IN YOUR NOTES STATES TYPE
 OF BLDG. AS TYPE III. PLEASE SEE FBC
 SEC.311.2
  
 3) NOTO: FAIR HOUSING ANSI A117 CHANGES
 OF FLOOR LEVELS SEE SEC. 303.3 WHICH IS
 1/4" ALLOWED. SEE SEC.303.4 BEVELS USED
 ON THRESHOLDS MAX HEIGHT IS 1/2".
  
  
 4) FLOOR: THE THICKNESS OF PLYWOOD SEE
 FBC CH 8 SEC.803.7.2. TYPE II
 CONSTRUCTION INSULATING BOARD SHOULD NOT
 BE MORE THAN 1/2"
  
 ) PLEASE SUBMIT ADDITIONAL DETAILS
 TO SHOW ATTATCHMENT AND FASTENING OF
 MATERIALS TO FLOOR AND CEILING DECK.
  
 6) SUBMIT TYPE OF BACKING TO BE USED IN
 ALL WALLS. SEE SHEET A.8 DETAIL#3
 609.2.1 FIRE RETARDENT TREATED WOOD.
  
  
 7) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY. ALSO SEE SEC.803.4
  
  