2004-06-04 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) SHT P-2 SANITARY RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| MEET CODE REQUIREMENTS: |
| A) SECTION 909.1 ONLY THE FIXTURES WITH |
| IN THE BATHROOM GROUPS SHALL CONNECT TO |
| THE WET-VENTED HORIZONTAL BRANCH DRAIN. |
| ANY ADDITIONAL FIXTURES SHALL DISCHARGE |
| DOWNSTREAM OF THE WET VENT. (SEE WASH |
| MACHINE). |
| B) THE MASTER BATH IS SHOWN FIRST ON |
| THE FLOOR PLAN, BUT ON THE RISER DIAGRAM |
| IT IS SHOWN IN THE MIDDLE OF THE FLOOR |
| PLAN. PLEASE CLAIRFY. SECTION 104.2.1 |
| C) CABANA BATH SHOWN ON FLOOR PLAN IS |
| NOT SHOWN ON RISER DIAGRAM. SEC. 104.2.1 |
| 2) THE FOLLOWING INFORMATION IS REQUIRED |
| TO BE SUBMITTED FOR GAS PERMIT: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| 3)A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| SPECIFICATIONS, REPORTS AND FINAL BID |
| DOCUMENTS PROVIDED TO THE OWNER OR THE |
| OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| MENTS PREPARED OR ISSUED BY SAID REGIS- |
| TRANT AND BEING FILED FOR PUBLIC RECORD. |
| THE DATE THAT THE SIGNATURE AND SEAL IS |
| AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| UNDER THE SIGNATURE OF THE PROFESSIONAL |
| ENGINEER, FAC 61G15-23.002(1) |
| FS 471.025 |
| EACH SHEET OF PLANS AND PRINTS WHICH |
| MUST BE SEALED UNDER THE PROVISIONS OF |
| CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| DATED BY THE PROFESSIONAL ENGINEER IN |
| RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| FS 471.025 |
| ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| SHEET. IF PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME AND LICENSE NUMBER, AS WELL |
| AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING |
| BUSINESS ON EACH SHEET. A TITLE BLOCK |
| WILL SATISFY THIS REQUIREMENT. FAC |
| 61G15-23.002(2) - FS 471.025 |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |