Plan Review Notes
Plan Review Notes For Permit 04060157
Permit Number 04060157
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-03 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE THAT ON SHEET E-1 THE FOLLOWING
 ITEMS NEED CORRECTIONS.
  
 1} THE BEDROOM NEEDS TWO RECEPTACLES
 ADDED TO COMPLY WITH 210.52(A)&(B).
  
 2} THE LOCATION OF THE A/C DISCONNECTS
 DO NOT COMPLY WITH CLEARANCE
 REQUIREMENTS OF 110.26.
  
 PLEASE SEE THAT THESE CORRECTIONS ARE
 MADE PRIOR TO ROUGH INSPECTION AND
 REVISED ON THE PLAN BEFORE C.O..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW