 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ELECTRICAL RISER INDICATES THE
 SERVICE IS EXISTING. SHOW LOCATION OF
 SERVICE. THIS IS CONFUSING DO TO THE
 FACT THE RESIDENCE HAS NOT YET BEEN
 CONSTRUCTED.
  
 2} PLEASE PROVIDE PANEL SCHEDULES AND
 LOADS FOR ALL PANELS. WHAT DOES THE 2ND
 METER AND PANEL "K" SERVE?
  
 3} THE GRONDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250.50 "EACH ITEM",
 INCLUDING FOOTER STEEL, (UFER GROUND).
  
 4} THE GARAGE RECEPTACLES MUST BE GFCI
 PROTECTED PER 210.8(A)(2).
  
 5} PROVIDE SMOKE DETECTORS PER
 8-1.4.1.6.2 NFPA-72 & 905.2.2 FBG, SEE
 SHEET E-1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  