Plan Review Notes
Plan Review Notes For Permit 04060157
Permit Number 04060157
Review Stop B
Sequence Number 1
Notes
Date Text
2004-07-01 00:00:00DENIED
  
 1) THE NOTICE OF COMMENCEMENT HAS NO
 DESCRIPTION OF WORK ON IT. SEE FS 713.13
 SUBMIT RECORDED COPY OF NOC WITH ALL
 REQUIRED INFORMATION.
  
 2) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 3) THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN OF THE
 STRUCTURE IS REQUIRED ON EACH SHEET OF
 THE DRAWINGS PER FBC 104.2.1.
  
 4) SPECIFY THE BUILDING CATEGORY ON THE
 PLANS AS REQUIRED BY FBC 1606.1.7 (2).
  
 5) SPECIFY THE DESIGN CRITERIA USED TO
 DESIGN THE STRUCTURE TO RESIST THE WIND
 LOADS IN FBC 1606 AND COMBINED LOADS IN
 FBC 1609.
  
 6) THE FIRST FLOOR BATHROOM IS REQUIRED
 TO HAVE A DOOR WITH A 29" CLEAR OPENING.
 SEE FBC 11-4.22.2.
  
 7) THE EGRESS WINDOWS IN THE SCHEDULE
 ARE 24-5 WINDOWS.
  
 8) THE "+" FOR SECOND STORY TIE DOWNS
 ON A2 AND A5 ARE NOT CLEAR AS TO THE
 SPACING. IS THIS INDICATING THE FLOOR
 TRUSS CONNECTORS AT 2'OC OR THE WALL TO
 FLOOR TRUSS CONNECTIONS AT 4'OC? PLEASE
 CLARIFY.
  
 10) CLARIFY THE LOCATIONS OF THE HD5
 HOLDDOWN CONNECTORS. GIVE SPACING
 DIMENSIONS. NO HOLDOWNS ARE SPECIFIED
 AT THE SECOND FLOOR WEST WALL. INDICATE
 THE SECOND FLOOR SHEAR WALLS.
  
 11) FBC 1503.4.4 REQUIRES GUTTERS AND
 DOWN SPOUTS ON ROOFS WITH LESS THAN 6"
 OF OVERHANG WITH WATER DISCHARGED ONE
 FOOT FROM STRUCTURE. SIZE AND DISCHARGE
 OF ROOF GUTTERS, SCUPPERS, ETC. PER FBC
 PLUMBING. SPECIFY THIS FOR THE FLAT ROOF
 AT GARAGE AND DECK.
  
 12) SPECIFY THE 1-1/2" BLOCK RECESS
 WATERSTOP WHERE THE MASONRY WALL BEARS
 ON THE CONCRETE FLOOR. SEE CITY OF WPB
 AMENDMENTS TO FBC 2111.1.9.
  
 13) SPECIFY THE EMBEDMENT DEPTH OF THE
 3" DIAMETER PIPE COLUMN AT THE LOGGIA.
  
 14) CLARIFY THE COLUMNS INDICATED ON A4
 WITH THE TWO REINFORCING BARS. ARE THESE
 8 X 16 BLOCK WITH 2 REINFORCED FILLED
 CELLS?
  
 15) A5 SHOWS META 24 CONNECTORS FOR THE
 GARAGE ROOF AND D1 ON A8 SHOWS HETA 20
 CONNECTORS. PLEASE CLARIFY.
  
 16) DETAIL 1 ON A6 SHOULD THIS BE A SPH6
 CONNECTOR INSTEAD OF HPH6 ?
  
 17) SPECIFY THE BUCK ATTACHMENT FOR THE
 DOORS.
  
 18) THE UPLIFT VALUE FOR THE META 24
 CONNECTORS IS INCORRECT. IT SHOULD BE
 1450#. SEE 2004 SIMPSON CATALOG.
  
 19) PLEASE CLARIFY THE FOOTING THICKNESS
 DIMENSIONS LISTED ON A6. TOP OF FINISH
 FLOOR IS REQUIRED TO BE A MINIMUM OF 4"
 ABOVE FINAL GRADE AND BOTTOM IS REQUIRED
 TO BE MINIMUM OF 12" BELOW GRADE. FBC
 1804.1.3 AND CITY AMEND. 1804.1.7.
  
 20) THE UPLIFT VALUE OF THE HETA 20 ON
 A8 IS INCORRECT. IT SHOULD BE 1810# PER
 2004 SIMPSON CATALOG.
  
 21) THE STRUCTURE IS TYPE VI. PLEASE
 REVISE NOTE ON A8.
  
 22) CLARIFY THE 2 DIMENSIONS GIVEN FOR
 THE FOOTER WIDTH IN DETAIL 1 ON A9.
  
 23) THE DESIGN PRESSURE IN THE TABLE ON
 A9 IS INCORRECT FOR THE POSITIVE
 INTERIOR ZONE FOR 0-15 SQFT OPENINGS.
 SHOULD BE +35.3.
  
 24) SPECIFY THE POSITIVE AND NEGATIVE
 OPENING PRESSURES FOR EACH WINDOW AND
 DOOR OPENING ON THE ELEVATIONS.
  
 25) THE WELDED POST CAP & POST ASSEMBLY
 ON A9 IS REQUIRED TODESIGNED BY AN
 ARCHITECT OR ENGINEER.
  
 26) SPECIFY THE EDGE DISTANCE AND CENTER
 TO CENTER SPACING OF THE REDHEADS USED
 TO ATTACH THE GARAGE DOOR BUCK ON SHEET
 A10.
  
 27) FIREBLOCKING IS REQUIRED AT THE
 CONCEALED SPACE BETWEEN STAIR STRINGERS
 AT THE TOP AND BOTTOM OF RUNS PER FBC
 2305.1.4. SPECIFY ON A11 AND A12.
  
 28) FBC 1007.8.1 REQUIRES WINDERS TO
 HAVE A MINIMUM TREAD WIDTH OF 6" AND A
 MINIMUM TREAD DEPTH OF 11" AT A POINT
 12" FROM THE NARROW EDGE. SPECIFY THIS
 ON PLANS.
  
 29) CHECK CALCULATIONS FOR UPLIFT AT HIP
 ROOF GIRDER TRUSSES ON A13. UPLIFT MAY
 EXCEED 1260# AT THESE LOCATIONS.
  
 30) SUBMIT STATE PRODUCT APPROVALS FOR
 OVERHEAD GARAGE DOOR, STRUCTURAL
 MULLIONS, STANLEY 6-PANEL DOOR, TRUSS
 CONNECTORS.
  
 31) PLEASE CLARIFY ON A1 WHICH WINDOWS
 AND DOORS ARE TO BE IMPACT RESISTANT AND
 WHICH WILL BE SHUTTERED.
  
 SEE NOTES IN RED PENCIL ON THE PLANS.
  