2004-07-01 00:00:00 | DENIED |
| |
| 1) THE NOTICE OF COMMENCEMENT HAS NO |
| DESCRIPTION OF WORK ON IT. SEE FS 713.13 |
| SUBMIT RECORDED COPY OF NOC WITH ALL |
| REQUIRED INFORMATION. |
| |
| 2) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 3) THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN OF THE |
| STRUCTURE IS REQUIRED ON EACH SHEET OF |
| THE DRAWINGS PER FBC 104.2.1. |
| |
| 4) SPECIFY THE BUILDING CATEGORY ON THE |
| PLANS AS REQUIRED BY FBC 1606.1.7 (2). |
| |
| 5) SPECIFY THE DESIGN CRITERIA USED TO |
| DESIGN THE STRUCTURE TO RESIST THE WIND |
| LOADS IN FBC 1606 AND COMBINED LOADS IN |
| FBC 1609. |
| |
| 6) THE FIRST FLOOR BATHROOM IS REQUIRED |
| TO HAVE A DOOR WITH A 29" CLEAR OPENING. |
| SEE FBC 11-4.22.2. |
| |
| 7) THE EGRESS WINDOWS IN THE SCHEDULE |
| ARE 24-5 WINDOWS. |
| |
| 8) THE "+" FOR SECOND STORY TIE DOWNS |
| ON A2 AND A5 ARE NOT CLEAR AS TO THE |
| SPACING. IS THIS INDICATING THE FLOOR |
| TRUSS CONNECTORS AT 2'OC OR THE WALL TO |
| FLOOR TRUSS CONNECTIONS AT 4'OC? PLEASE |
| CLARIFY. |
| |
| 10) CLARIFY THE LOCATIONS OF THE HD5 |
| HOLDDOWN CONNECTORS. GIVE SPACING |
| DIMENSIONS. NO HOLDOWNS ARE SPECIFIED |
| AT THE SECOND FLOOR WEST WALL. INDICATE |
| THE SECOND FLOOR SHEAR WALLS. |
| |
| 11) FBC 1503.4.4 REQUIRES GUTTERS AND |
| DOWN SPOUTS ON ROOFS WITH LESS THAN 6" |
| OF OVERHANG WITH WATER DISCHARGED ONE |
| FOOT FROM STRUCTURE. SIZE AND DISCHARGE |
| OF ROOF GUTTERS, SCUPPERS, ETC. PER FBC |
| PLUMBING. SPECIFY THIS FOR THE FLAT ROOF |
| AT GARAGE AND DECK. |
| |
| 12) SPECIFY THE 1-1/2" BLOCK RECESS |
| WATERSTOP WHERE THE MASONRY WALL BEARS |
| ON THE CONCRETE FLOOR. SEE CITY OF WPB |
| AMENDMENTS TO FBC 2111.1.9. |
| |
| 13) SPECIFY THE EMBEDMENT DEPTH OF THE |
| 3" DIAMETER PIPE COLUMN AT THE LOGGIA. |
| |
| 14) CLARIFY THE COLUMNS INDICATED ON A4 |
| WITH THE TWO REINFORCING BARS. ARE THESE |
| 8 X 16 BLOCK WITH 2 REINFORCED FILLED |
| CELLS? |
| |
| 15) A5 SHOWS META 24 CONNECTORS FOR THE |
| GARAGE ROOF AND D1 ON A8 SHOWS HETA 20 |
| CONNECTORS. PLEASE CLARIFY. |
| |
| 16) DETAIL 1 ON A6 SHOULD THIS BE A SPH6 |
| CONNECTOR INSTEAD OF HPH6 ? |
| |
| 17) SPECIFY THE BUCK ATTACHMENT FOR THE |
| DOORS. |
| |
| 18) THE UPLIFT VALUE FOR THE META 24 |
| CONNECTORS IS INCORRECT. IT SHOULD BE |
| 1450#. SEE 2004 SIMPSON CATALOG. |
| |
| 19) PLEASE CLARIFY THE FOOTING THICKNESS |
| DIMENSIONS LISTED ON A6. TOP OF FINISH |
| FLOOR IS REQUIRED TO BE A MINIMUM OF 4" |
| ABOVE FINAL GRADE AND BOTTOM IS REQUIRED |
| TO BE MINIMUM OF 12" BELOW GRADE. FBC |
| 1804.1.3 AND CITY AMEND. 1804.1.7. |
| |
| 20) THE UPLIFT VALUE OF THE HETA 20 ON |
| A8 IS INCORRECT. IT SHOULD BE 1810# PER |
| 2004 SIMPSON CATALOG. |
| |
| 21) THE STRUCTURE IS TYPE VI. PLEASE |
| REVISE NOTE ON A8. |
| |
| 22) CLARIFY THE 2 DIMENSIONS GIVEN FOR |
| THE FOOTER WIDTH IN DETAIL 1 ON A9. |
| |
| 23) THE DESIGN PRESSURE IN THE TABLE ON |
| A9 IS INCORRECT FOR THE POSITIVE |
| INTERIOR ZONE FOR 0-15 SQFT OPENINGS. |
| SHOULD BE +35.3. |
| |
| 24) SPECIFY THE POSITIVE AND NEGATIVE |
| OPENING PRESSURES FOR EACH WINDOW AND |
| DOOR OPENING ON THE ELEVATIONS. |
| |
| 25) THE WELDED POST CAP & POST ASSEMBLY |
| ON A9 IS REQUIRED TODESIGNED BY AN |
| ARCHITECT OR ENGINEER. |
| |
| 26) SPECIFY THE EDGE DISTANCE AND CENTER |
| TO CENTER SPACING OF THE REDHEADS USED |
| TO ATTACH THE GARAGE DOOR BUCK ON SHEET |
| A10. |
| |
| 27) FIREBLOCKING IS REQUIRED AT THE |
| CONCEALED SPACE BETWEEN STAIR STRINGERS |
| AT THE TOP AND BOTTOM OF RUNS PER FBC |
| 2305.1.4. SPECIFY ON A11 AND A12. |
| |
| 28) FBC 1007.8.1 REQUIRES WINDERS TO |
| HAVE A MINIMUM TREAD WIDTH OF 6" AND A |
| MINIMUM TREAD DEPTH OF 11" AT A POINT |
| 12" FROM THE NARROW EDGE. SPECIFY THIS |
| ON PLANS. |
| |
| 29) CHECK CALCULATIONS FOR UPLIFT AT HIP |
| ROOF GIRDER TRUSSES ON A13. UPLIFT MAY |
| EXCEED 1260# AT THESE LOCATIONS. |
| |
| 30) SUBMIT STATE PRODUCT APPROVALS FOR |
| OVERHEAD GARAGE DOOR, STRUCTURAL |
| MULLIONS, STANLEY 6-PANEL DOOR, TRUSS |
| CONNECTORS. |
| |
| 31) PLEASE CLARIFY ON A1 WHICH WINDOWS |
| AND DOORS ARE TO BE IMPACT RESISTANT AND |
| WHICH WILL BE SHUTTERED. |
| |
| SEE NOTES IN RED PENCIL ON THE PLANS. |
| |
| IF YOU HAVE QUESTIONS PLEASE CALL: |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |