Plan Review Notes
Plan Review Notes For Permit 04060068
Permit Number 04060068
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-12 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) VACUUM LINE SHOWN ON PIPING SCHEMATIC
 IS NOT SHOWN ON POOL LAYOUT. CORRELATE
 PLANS. SECTION 104.2.1
 2) REVISION SHEET SHALL BE SIGNED AND
 SEALED WITH TITLE BLOCK INFORMATION OR
 BE INCORPORATED IN SIGNED/SEALED PLANS.
 SECTION 104.2.2
 3)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  