Plan Review Notes For Permit 04060031 |
Permit Number |
04060031 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | FBC-2001 CHAPTER 1 | | | | 1) PLANS INDICATE 3" PVC VENT PIPE, BUT | | MANUF. INFORMATION STATES VENT HOODS MAY | | BE EXTREAMLY HOT DURING OPERATION. | | PLEASE CLARIFY. SUBMIT MANUF INFO FOR | | THE VENTING. | | 2) PIPE SIZE FROM METER TO EXISTING TEE | | SHALL BE CHANGED TO 1-1/2" PER TABLE | | 402(2) FOR 620,000 BTU'S @ 50 FEET. | | 3) ALL INFORMATION, DRAWINGS, SPECIFIC- | | ATIONS AND ACCOMPANYING DATA SHALL BEAR | | THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|