2004-06-04 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| IT IS NOTED THAT THE EXISTING ROOF |
| STRUCTURE WILL BE GENERALLY REINFORCED |
| BUT, IN ADDITION, THE "PARAPET & CRICKET |
| MODIFICATION DETAIL" REQUIRES AMENDMENT |
| AS FOLLOWS: |
| |
| 1) FBC 2108.2.1HOW IS THE NEW PARAPET |
| WALL TIED TO THE EXISTING SLAB/WALL |
| BELOW?AMEND THE DETAIL TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 2) FBC 2319.12.2COLLAR TIES.THE CUT |
| ENDS OF THE RAFTERS SHALL BE TIED/BRACED |
| BACK TO THE CONCRETE SLAB TO RESIST THE |
| HORIZONTAL THRUST FROM THE INCLINED |
| RAFTER.AMEND THE DETAIL. |
| |
| 3) FBC 1601.2.1NEW FRAMING UNDER |
| RAFTER TO RESIST UPLIFT AND GRAVITY |
| LOADS.THE DETAIL DOES NOT STATE WHAT |
| IS THE SIZE (AND SPACING) OF THE MEMBERS |
| TO BE USED FOR THIS FRAMING, HOW IT IS |
| TO BE TIED TO THE SLAB/WALL BELOW, HOW |
| THE RAFTER IS SEATED ON THE TOP PLATE OR |
| WHAT IS THE CALCULATED UPLIFT AND |
| MANUFACTURERS REFERENCE FOR THE RAFTER |
| UPLIFT ANCHOR.AMEND THE DETAIL TO |
| CLARIFY ALL OF THESE ITEMS. |
| |
| 4) 61G15-23.002(1)FL. ADMIN. CODE. |
| PLANS SIGNED & SEALED BY A PROFESSIONAL |
| ENGINEER SHALL INCORPORATE THE FULL |
| SIGNATURE OF THE ENGINEER.THE |
| SIGNATURE ON THE SUBMITTED SHEETS IS NOT |
| THE FULL SIGNATURE OF RIZA NUR ALTAN,P.E |
| THE SHEET ATTACHED TO THESE COMMENTS, |
| FOR YOUR INFORMATION, SHOWS THE FULL |
| SIGNATURE.WE HAVE RECENTLY CONTACTED |
| THE FLORIDA BOARD OF ENGINEERS ABOUT |
| SIMILAR CASES AND THEY HAVE ADVISED THAT |
| PROFESSIONAL ENGINEER'S SIGNATURES |
| SHOULD INCORPORATE A LEGIBLE FIRST AND |
| LAST NAME.INITIALS ARE NOT SUFFICIENT. |
| RIZA NUR ALTAN, P.E. SHALL PROVIDE A |
| FULL SIGNATURE ON EACH RESUBMITTED SHEET |
| OR SUBMIT A NOTARIZED SIGNED/SEALED |
| LETTER STATING THAT THE SIGNATURE ON THE |
| LETTER IS THE SAME AS THAT HELD ON FILE |
| BY THE FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS.THAT LETTER WILL BE |
| SUBMITTED TO THE BOARD FOR VERIFICATION. |
| (471.025 F.S.). |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |