Plan Review Notes For Permit 04051244 |
Permit Number |
04051244 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-02-25 00:00:00 | ************ UNSAT ************ | | | | 1)NOTE: PLEASE SEE ORIG REDLINES FROM | | REIVEW 6/04 BY JAKE LEAHY, PLEASE SEE | | NOTE #7 ON RISER IS MISSING FROM "NOTES | | LEGEND". | | | | 2)NOTE: PLEASE CLARIFY METHOD OF | | EQUIPMENT GROUNDING BETWEEN MDP TO | | PANELS. | | 250.110,250.122 | | | | 3)NOTE: PLEASE SEE ORIG PLANS CALLED FOR | | A MCB IN MDP AND NOW MDP IS SHOWN AS MLO | | AND IS SHOWING MORE THAN 6-SPACES. | | PLEASE SEE 230.71A | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|