Plan Review Notes
Plan Review Notes For Permit 04051244
Permit Number 04051244
Review Stop P
Sequence Number 2
Notes
Date Text
2004-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
  
 FROM PREVIOUS REVIEW:
 3) SHT A-114 DETAIL 1 SHOW MEASUREMENT
 FROM THE CENTER OF W/C TO WALL. FIG 28
 REVISION SHOWS 1'10". 1'6" REQUIRED.
 9) SUBMIT STORM RISERS FOR SECONDARY
 ROOF DRAINS. SHOW PIPE SIZES AND SLOPE.
 INDICATE TERMINATION POINT. SECTION
 104.3.1.1
  
 NEW COMMENTS:
 1B) SHT MP-101 4" HORIZONTAL LEADER AT
 1/4" PER FT. NOT SUFFICIENT FOR 2,470 SF
 PER TABLE 1106.3- ALSO IF HORIZONTAL
 LEADER ON SECONDARY DRAIN, THEN MINIMUM
 5" REQUIRED FOR AREAS AT ROOF DRAINS
 #'S 1 & 4 AND 8" REQUIRED FOR AREAS AT
 ROOF DRAINS #'S 2 & 3.
 2B) SHOW SIZE AND LOCATION OF SECONDARY
 ROOF DRAINS FOR THE LOWER ROOFS. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]