Plan Review Notes
Plan Review Notes For Permit 04051244
Permit Number 04051244
Review Stop B
Sequence Number 2
Notes
Date Text
2004-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051244
 ADD: 3021 OKEECHOBEE BLVD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7133
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVISO: NO SOILS REPORT TO BE
 SUBMITTED, CONTRACTOR/ DESIGN PROFESSION
 ALS WILL BE CONTINUING WORK AT OWN RISK.
 WILL BE STATED ON PERMIT CARD!!!!
  
 3) SUBMITTED ENERGY CALCULATIONS:
 FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EFIS-(PAREXEIFS)
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 NOTE***** PROVIDE NOC FOR BOTH
 HORIZONTAL AND VERTICAL APPLICATIONS.
  
 5) PROVIDE THE FIRE RATING REPORT FOR
 THE EFIS SYSTEM, SINCE THIS STRUCTURE IS
 IN A FIRE ZONE EXTERIOR WALLS ARE TO BE
 NON-COMBUSTIBLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026