2004-07-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04051244 |
| ADD: 3021 OKEECHOBEE BLVD |
| CONT: POPPER AND ASSOCIATES |
| TEL: (561)719-7133 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) PROVISO: NO SOILS REPORT TO BE |
| SUBMITTED, CONTRACTOR/ DESIGN PROFESSION |
| ALS WILL BE CONTINUING WORK AT OWN RISK. |
| WILL BE STATED ON PERMIT CARD!!!! |
| |
| 3) SUBMITTED ENERGY CALCULATIONS: |
| FBC 13-103.1.2 BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, THE SUBMITTED |
| ENERGY CODE COMPLIANCE FORMS SHALL BE |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| |
| 4) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) EFIS-(PAREXEIFS) |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| NOTE***** PROVIDE NOC FOR BOTH |
| HORIZONTAL AND VERTICAL APPLICATIONS. |
| |
| 5) PROVIDE THE FIRE RATING REPORT FOR |
| THE EFIS SYSTEM, SINCE THIS STRUCTURE IS |
| IN A FIRE ZONE EXTERIOR WALLS ARE TO BE |
| NON-COMBUSTIBLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |