2004-06-18 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) ALL ARCHITECTURAL SHEET SHALL BE SEA- |
| LED AND DATED PER FAC 61G1-16.003 AND |
| FS 481.2055. |
| 2) SHT A-114 SHOW CLEAR FLOOR SPACE FOR |
| SINK IN BREAK ROOM. SECTION 11-4.24.5 |
| 3) SHT A-114 DETAILS 1 AND 15 SHOW THE |
| MEASURMENT FROM THE CENTER OF THE LAVS & |
| WATER CLOSETS TO THE WALL. FIG 28. 18" |
| FOR W/C AND 15" FOR LAV. |
| 4) SHT A-114 HANDICAP SINK AT COUNTER |
| DETAIL SHALL BE MAXIMUM 34" PER SECTION |
| 11-4.24.2. DETAIL SHOWS 68" |
| 5) SHTS A-103 & MP-101 SHOW SECONDARY |
| ROOF DRAINS IN DIFFERENT LOCATIONS. |
| CORRELATE PLANS. SECTION 104.2.1 |
| 6) SHT MP-100 SUBMIT CALCULATIONS FOR |
| UPPER AND LOWER ROOFS. SHOW SF FOR EACH |
| AREA AND SHOW 1/2 AREA OF VERTICAL WALLS |
| INCLUDING PARAPETS ADDED TO CALCULATIONS |
| FOR EACH AREA. THEN SHOW TOTAL ROOF AREA |
| DRAINING TO EACH ROOF DRAIN. SECTIONS |
| 1106, 1107 AND ALL SUBSECTIONS. |
| 7) SHT P-201 URINAL SHALL CONNECT DOWN- |
| STREAM OF THE LAV ON THE STACK IN THE |
| MEN'S TOILET ROOM. SECTION 1104.2.1 |
| 8) SHT P-201 BREAK ROOM SINK SHALL DIS- |
| CHARGE DOWNSTREAM OF THE FIXTURES IN THE |
| WOMENS TOILET ROOM. SECTION 909.1 |
| 9) SUBMIT STORM RISERS FOR THE PRIMARY |
| AND SECONDARY ROOF DRAINS, AND SUBMIT |
| BLDG STORM ISOMETRICS. SHOW ALL PIPE |
| SIZES AND SLOPE. INDICATE TERMINATION |
| POINT FOR EACH SYSTEM. |
| 10) SHT P-201 PLUMBING SPECIFICATIONS, |
| MATERIALS, (F) AIR CHAMBERS ARE NOT |
| APPROVED. DELETE FROM REFERENCE. SECTION |
| 604.9 |
| |