Plan Review Notes
Plan Review Notes For Permit 04051244
Permit Number 04051244
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL ARCHITECTURAL SHEET SHALL BE SEA-
 LED AND DATED PER FAC 61G1-16.003 AND
 FS 481.2055.
 2) SHT A-114 SHOW CLEAR FLOOR SPACE FOR
 SINK IN BREAK ROOM. SECTION 11-4.24.5
 3) SHT A-114 DETAILS 1 AND 15 SHOW THE
 MEASURMENT FROM THE CENTER OF THE LAVS &
 WATER CLOSETS TO THE WALL. FIG 28. 18"
 FOR W/C AND 15" FOR LAV.
 4) SHT A-114 HANDICAP SINK AT COUNTER
 DETAIL SHALL BE MAXIMUM 34" PER SECTION
 11-4.24.2. DETAIL SHOWS 68"
 5) SHTS A-103 & MP-101 SHOW SECONDARY
 ROOF DRAINS IN DIFFERENT LOCATIONS.
 CORRELATE PLANS. SECTION 104.2.1
 6) SHT MP-100 SUBMIT CALCULATIONS FOR
 UPPER AND LOWER ROOFS. SHOW SF FOR EACH
 AREA AND SHOW 1/2 AREA OF VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO CALCULATIONS
 FOR EACH AREA. THEN SHOW TOTAL ROOF AREA
 DRAINING TO EACH ROOF DRAIN. SECTIONS
 1106, 1107 AND ALL SUBSECTIONS.
 7) SHT P-201 URINAL SHALL CONNECT DOWN-
 STREAM OF THE LAV ON THE STACK IN THE
 MEN'S TOILET ROOM. SECTION 1104.2.1
 8) SHT P-201 BREAK ROOM SINK SHALL DIS-
 CHARGE DOWNSTREAM OF THE FIXTURES IN THE
 WOMENS TOILET ROOM. SECTION 909.1
 9) SUBMIT STORM RISERS FOR THE PRIMARY
 AND SECONDARY ROOF DRAINS, AND SUBMIT
 BLDG STORM ISOMETRICS. SHOW ALL PIPE
 SIZES AND SLOPE. INDICATE TERMINATION
 POINT FOR EACH SYSTEM.
 10) SHT P-201 PLUMBING SPECIFICATIONS,
 MATERIALS, (F) AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM REFERENCE. SECTION
 604.9
  
 REVIEW BY KEN STEVENS