Plan Review Notes
Plan Review Notes For Permit 04051140
Permit Number 04051140
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-10 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ATTACHED SHEET WITH REVISIONS 1 THRU
 6 SHALL BE SIGNED AND SEALED BY ENGINEER
 OF RECORD WITH PROPER TITLE BLOCK, OR
 NOTES SHALL BE INCORPORATED IN PLANS
 THAT ARE SIGNED AND SEALED BY ENGINEER
 OF RECORD.
 2) VACUUM LINE SHOWN ON PIPING SCHEMATIC
 IS NOT SHOWN ON POOL LAYOUT/PIPING.
 PLEASE CORRELATE PLANS. SECTION 104.2.1
 3)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  