2004-06-02 00:00:00******** UNSAT *************
  
 1)NOTE: PLANS ARE TO CONTAIN PRINTED
 NAME AND SIGNATURE OF PERSON RESPONSIBLE
 FOR PLANS. FBC 104.2.1
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND LOAD CALCULATIONS. THERE ARE SOME
 ITEMS ON PANEL SCHEDULE THAT ARE NOT
 SHOWN IN LOAD CALCS. WHPL TUB/
 POOL HTR IN LOAD CALCS BUT NOT ON PANEL
 SCHEDULE? SEE POOL EQUIPMENT? #8 30A?
  
  
 3 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  