2004-07-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051036
 ADD: 4512 N FLAGLER DR
 CONT: MHS CONSTRUCTION
 TEL: (561)282-8220
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT INDICATE THE WINDOW
 SIZES, NEW AWNING IS COVERING THE
 GLAZING. THE PLANS DO NOT INDICATE
 THE WIDTH OR HEIGHT OF GLAZING UNITS,
 IN WHICH DIRECTION THE MULLIONS RUN,
 LENGHT OF MULLIONS. SUBMITTED THE STATE
 COVER SHEET FOR MULLIONS BUT NO REPORT.
  
 2) PRODUCT TESTING REPORTS SUBMITED HAVE
 BEEN REDUCED, THEY ARE UNLEGIBLE AND NOT
 SUITABLE FOR DUPLICATION FOR RECORD
 MANAGEMENT. 104.2.1.3. QUALITY OF PLANS.
 PRODUCT TESTING REPORTS THAT HAVE MULTI-
 PLE GLAZING CHARTS, NEITHER THE DESIGN
 PROFESSIONAL NOR THE CONTRACTOR HAS
 HIGHLIGHTED WHICH PRODUCT WILL BE USED
 IN THIS APPLICATION. WE CAN NOT DETER-
 MINE IF THE PRODUCT MEETS THE REQUIED
 PRESSURES.
  
 3) EXISTING STAIRWELLS ARE MISSING EXIT
 DOORS ON THE 2ND AND 3RD FLOOR.
 1006.1.4 THERE SHALL BE NO ENCLOSED
 USEABLE SPACE WITHIN AN EXIT ENCLOSUE,
 INCLUDING UNDER STAIRS.
 1006.1.3.1 PENETRATIONS INTO AND
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR THE INDEPENDENT STAIR PRESSURIZATION
 SPRINKLER PIPING, STANDPIPES AND ELECTRI
 CALCONDUIT SERVING THE STAIRWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO
 TECTED IN ACCORDANCE WITH 705.4
 1006.1 EXIT STAIRWAYS BETWEEN FLOORS
 SHALL BE ENCLOSED IN OR SEPERATED BY
 FIRE RESISTANT CONSTRUCTION IN ACCORD-
 ANCE WITH 705.2 OR 705.1.2.
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026