2004-06-08 00:00:00DENIED:
 1.PLANS INDICATE NEW ATRIUM.PLEASE
 PROVIDE THE FOLLOWING INFORMATION FOR
 REVIEW:
 - HEIGHT OF ATRIUM
 - VOLUME OF ATRIUM, CUBIC FT.
 REFERENCE 2001 FBC(M) 403.6.6.1.
  
 2.PLEASE CLARIFY EQUIPMENT SCHEDULE
 SHOWN ON PLAN SHEET ME2, AHU SCHEDULE
 INDICATES TWO AHU-5 WHEREAS THE FLOOR
 PLAN INDICATES AHU-1 & 2.
  
 3.ARE THE TWO AHU'S GOING TO SUPPLY
 THE UNFINISHED AREAS WITH VENTILATION OR
 WILL THIS BE SEPARATE?
  
 4.PROVIDE INFORMATION ON SEPARATION
 BETWEEN THE CORRIDORS AND UNFINISHED
 SPACES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.