Plan Review Notes
Plan Review Notes For Permit 04051036
Permit Number 04051036
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051036
 ADD: 4512 N FLAGLER DR
 CONT: MHS CONSTRUCTION
 TEL: (561)282-8220
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".MINIMUM ELE. 7'-6"
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT SYSTEM W/ LARGE MISSLE
 IMPACT TESTING
 B) MULLIONS
 C) EXTERIOR DOORS
 D) GUARDRAILS- SEE RULE 9B-72
 E) ROOFING ASSEMBLIES
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) 414.3 ATRUIMS. AN APPROVED AUTOMATIC
 FIRE SPRINKLER SYSTEM SHALL BE INSTALLED
 THROUGHOUT THE ENTIRE BUILDING.
  
 7) SEE 414.2 SMOKE CONTROL FOR LESS THAN
 600,000 CU FT. A SMOKE EXHAUST SYSTEM
 SHALL BE LOCATED AT THE CEILING OF THE
 ATRIUM.SUCH SYSTEM SHALL EXHAUST 40,000
 CFM.
  
 8) 414.3 SUPPLY AIR INLETS MAY BE PRO-
 VIDED AT THE LOWEST LEVEL OF THE ATRIUM.
  
 9) SMOKE CONTROL 414.1 UPON DETECTION
 OF A FIRE THE SYSTEM SHALL SHUT DOWN THE
 AIR SUPPLY TO THE FIRE FLOOR AND THE RE-
 TURN AIR FROM ALL NON FIRE FLOORS.
  
 10) 3RD FLOOR, WEST END. 414.5 1-HR FIRE
 SEPERATION FROM ADJACENT SPACES, OR SEE
 AUTO SPRINKLER SPACING.
  
 11) 414.6 AUTO FIRE DETECTERS.
  
 12) 414.7 STANDBY POWER.
  
 13)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 14) 1015.2 GUARDRAILS ARE TO BE A MINI-
 MUM OF 42" TALL.
  
 15) FBC 1608.2.2THE GUARDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 16) SHEET A2 INDICATES NEW A/C CLOSET
 WHERE WILL THIS UNIT SUPPLY AIR TO?
  
 17)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved