2005-02-23 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE CORRELATE RTU OCP WITH
 RTU'S NOTED ON BOTTOM OF E-3.
 PLEASE CLARIFY A/C SYSTEM. PANEL
 SCHEDULE INDICATES RTU'S AND AHU'S? ARE
 THE RTU'S COND UNITS?
 PLEASE ALSO CORRELATE WITH PLANS.
  
 2)NOTE: PLEASE SHOW SERVICE ENTRANCE
 CONDCUTORS PER 310.16,240.4.
 215.5
  
 3)NOTE: PLEASE SEE ANY HAND DRAWN
 CHANGES TO PLANS: EACH MUST BE SIGNED
 AND DATED BY THE ENGINEER OF RECORD. OR
 PLEASE REPRINT SHEETS WITH CHANGES AND
 SIGN, DATE AND SEAL SHEET.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  