Plan Review Notes
Plan Review Notes For Permit 04050953
Permit Number 04050953
Review Stop B
Sequence Number 2
Notes
Date Text
2004-08-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SWING OF DOORS 1 & 2 WERE
 CHANGED, A NOTE ABOUT 4 HR BLOCK WAS
 REMOVED; THESE CHANGES WERE NOT CLOUDED.
 WHAT OTHER CHANGES WERE MADE TO THE
 PLAN WHICH WERE NOT CLEARLY INDICATED?
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)INSULATION IS REQUIRED IN THE
 TENANT PARTITION WALLS, SEE PREVIOUS
 LIST ITEM #12.7-A10 DOES NOT SHOW
 THE REQUIRED INSULATION.
  
 4.)PROVIDE A LINTEL SCHEDULE.
  
 5.)SHEET E1 IS NOT SIGNED AND DATED.
  
 6.)SEE PREVIOUS LIST, ITEM #13 IN
 PROVIDING PRODUCT APPROVALS:
 EXTERIOR DOORS
 STOREFRONT WINDOWS AND DOORS, TRANSOM
 FIXED GLASS WINDOWS
 MULLIONS
 NOTE - ALL GLAZING TO BE IMPACT AS PER
 PLAN.
  
 7.)SEE PREVIOUS LIST, ITEM #14.
 BEFORE RESUBMITTING, HAVE THE NEW
 SHEETS APPROVED BY HISTORIC.
  
 8.)THERE IS A NOTE FROM YOUR GLASS
 SUPPLIER STATING THAT THE HEIGHTS ARE
 TOO LARGE FOR THE STOREFRONT SYSTEM.
 AS PRODUCT APPROVALS WERE NOT SUBMITTED
 FOR THE STOREFRONT, PLEASE ADDRESS
 AS APPLICABLE.
  
 9.)WHEN RESUBMITTING, CHANGE OUT ONLY
 REVISED SHEETS AND SUBMIT OLD SHEETS
 SEPARATELY.
  
 10.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 11.) THE PRINTED NAME OF THE PERSON
 SEALING THE PLAN IS TO BE ON EACH SHEET.
 FAC61G1-16.004.
  
 12.) SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC (PAGE 2).