2004-06-15 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) PERMIT APPLICATION STATES 5 BAYS, THE |
| PLANS SHOW 6 BAYS. CORRELATE APPLICATION |
| WITH PLANS. |
| 2) THE PERSNOAL SIGNATURE OF THE ARCHIT- |
| ECT SHALL APPEAR ON THE DOCUMENTS TO BE |
| FILED FOR PUBLIC RECORD. INITIALS ARE |
| NOT ACCEPTABLE. FAC 61G1-16.003 & FS |
| 481.2055. |
| 3) SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SECTIONS 1106 & |
| 1107. SHOW SQUARE FOOTAGE OF ROOF AND |
| SHOW 1/2 AREA OF ALL VERTICAL WALLS IN- |
| CLUDING PARAPETS ADDED TO AREA OF ROOF. |
| INDICATE SLOPE OF GUTTERS PER TABLE |
| 1106.6 AND SHOW HIGH POINTS OF GUTTER. |
| 4) INDICATE THE OCCUPANCIES OF THE BAYS. |
| TABLE 403.1 WILL DETERMINE WHICH FIXTUR- |
| ES WILL BE REQUIRED ACCORDING TO THE |
| OCCUPANCY OF EACH SPACE. DRINKING FOUNT- |
| AINS SHALL BE REQUIRED FOR EACH SPACE. |
| SEE SECTION 410.1. |
| 5) SHT P-1 PLUMBING NOTES: |
| #4 DIELECTRIC UNIONS ARE NOT APPROVED |
| FOR WATER DISTRIBUTION. DELETE REFERENCE |
| OR MODIFY TO READ DIELECTRIC COUPLING. |
| #6 AIR CHAMBERS ARE NOT APPROVED. DE- |
| LETE FROM REFERENCE. SECTION 604.9 |
| 6) AN RPZ BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE. SECTION 608.13.2 |
| 7) A WATER RISER DIAGRAM ISOMETRIC IS |
| REQUIRED. SECTION 104.3.1.1. |
| 8) OTHER COMMENTS MAY FOLLOW WHEN THE |
| OCCUPANCY IS ESTABLISHED. |
| |