Plan Review Notes
Plan Review Notes For Permit 04050953
Permit Number 04050953
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PERMIT APPLICATION STATES 5 BAYS, THE
 PLANS SHOW 6 BAYS. CORRELATE APPLICATION
 WITH PLANS.
 2) THE PERSNOAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON THE DOCUMENTS TO BE
 FILED FOR PUBLIC RECORD. INITIALS ARE
 NOT ACCEPTABLE. FAC 61G1-16.003 & FS
 481.2055.
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SECTIONS 1106 &
 1107. SHOW SQUARE FOOTAGE OF ROOF AND
 SHOW 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPETS ADDED TO AREA OF ROOF.
 INDICATE SLOPE OF GUTTERS PER TABLE
 1106.6 AND SHOW HIGH POINTS OF GUTTER.
 4) INDICATE THE OCCUPANCIES OF THE BAYS.
 TABLE 403.1 WILL DETERMINE WHICH FIXTUR-
 ES WILL BE REQUIRED ACCORDING TO THE
 OCCUPANCY OF EACH SPACE. DRINKING FOUNT-
 AINS SHALL BE REQUIRED FOR EACH SPACE.
 SEE SECTION 410.1.
 5) SHT P-1 PLUMBING NOTES:
 #4 DIELECTRIC UNIONS ARE NOT APPROVED
 FOR WATER DISTRIBUTION. DELETE REFERENCE
 OR MODIFY TO READ DIELECTRIC COUPLING.
 #6 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SECTION 604.9
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 7) A WATER RISER DIAGRAM ISOMETRIC IS
 REQUIRED. SECTION 104.3.1.1.
 8) OTHER COMMENTS MAY FOLLOW WHEN THE
 OCCUPANCY IS ESTABLISHED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]