2004-06-18 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)DECLARE AN OCCUPANCY CLASSIFICATION |
| AND OCCUPANT LOAD. |
| |
| 2.)SHEET LS1 IS INCORRECTLY LABELED |
| AS "PLUMBING PLAN". |
| |
| 3.)SEPARATE PERMITS REQUIRED FOR THE |
| AWNINGS, MECHANICAL, ROOF. |
| |
| 4.)THE FLOOR LIVE LOAD IS TO COMPLY |
| WITH FBC TABLE 1604.1, SHEET A1 (DESIGN |
| PARAMETERS). |
| |
| 5.)THIS IMPROVEMENT IS GREATER THAN |
| 50%, FBC3401.2.6. |
| |
| 6.)PROVIDE ENERGY CALCS, FBC400. |
| |
| 7.) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 8.) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 9.)TENANT SEPARATION REQUIRED FBC |
| 704.3.PROVIDE ASSEMBLY NUMBER OR |
| CALCULATED FIRE RESISTANCE FBC709. SHEET |
| A1 APPEARS TO INDICATE THE PARTITION |
| WALLS AS CONCRETE BLOCK 4HR, BUT REFERS |
| TO DETAIL 7-A10 WHICH IS METAL FRAME. |
| DETAIL 7-A10 REFERS TO UL U1165; I WAS |
| UNABLE TO FIND THIS IN THE UL BOOK OR |
| THE WEBSITE. |
| |
| 10.) SHEET A7 HAS BEEN CROSSED OFF WITH |
| A NOTE TO SEE REVISED A7.INCLUDE THIS |
| REVISED A7, APPROVED BY HISTORIC, WHEN |
| RESUBMITTING. |
| |
| 11.)DOORS 1 AND 2 ARE TO COMPLY WITH |
| FBC FIGURE 25, MANEUVERING CLEARANCES |
| AT DOORS, FOR BOTH PUSH AND PULL SIDES. |
| |
| 12.)INSULATION REQUIRED FOR COMMON |
| WALLS, FBC402. |
| |
| 13.)SUBMIT PRODUCT APPROVALS FOR THE |
| FOLLOWING: |
| EXTERIOR DOORS |
| STOREFRONT WINDOWS AND DOORS, TRANSOM |
| FIXED GLASS WINDOWS |
| MULLIONS |
| NOTE - ALL GLAZING TO BE IMPACT AS PER |
| PLAN |
| |
| 14.)BEFORE RESUBMITTING, HAVE THE |
| NEW SHEETS APPROVED BY HISTORIC. |