Date |
Text |
2004-11-03 00:00:00 | ********** UNSAT 3RD TIME ************ |
| |
| *** PLEASE SEE THE FOLLOWING COMMENTS |
| PLANS STILL CONTAIN CORRECTIONS THAT |
| NEED TO BE MADE THAT WERE ON PREVIOUS |
| TWO REVIEWS. |
| |
| 1)NOTE: PLEASE SEE PANEL IS SHOWN IN |
| KITCHEN ABOVE KITCHEN COUNTERSPACE. THIS |
| IS NOT PERMITTED. PLEASE SEE 110.26 FOR |
| MIN CLEARENCE REQUIREMENTS. |
| PREVIOUS REVIEW** |
| |
| 2)NOTE: PLEASE SEE RECEPT/GFI SPACING |
| ALONG KITCHEN COUNTERSPACE PER 210.52C1 |
| *PREVIOUS TWO REVIEWS** |
| |
| 3)NOTE: PLEASE SEE DINING RM/LIVING ROOM |
| STILL SHOWS #14 FOR REQUIRED 20A |
| CIRCUIT(S) FOR DINING RM.210.52B1 |
| **PREVIOUS TWO REVIEWS ** |
| |
| 4)NOTE:PLEASE SEE MISSING INFORMATION ON |
| TITLE BLOCK AS REQUIRED UNDER FAC |
| 61G15-23.002, FS 471 |
| **PREVIOUS REVIEW ** |
| |
| 5)NOTE: PLEASE SEE A NEW RISER DIAGRAM |
| IS NOW SUBMITTED AND IS NOW MISSING THE |
| REQUIRED FOOTER STEEL AS PART OF THE |
| G.E. SYSTEM. 250.50 |
| |
| *** PLEASE SEE ATTACHED COPY OF FS |
| 553.80(2)(B).*** |
| THIS REQUIRES ANY PLANS REVIEWED 3 OR |
| MORE TIMES WITH ANY OF THE SAME |
| COMMENTS |
| SHALL HAVE A 4X FEE ACCESSED TO THE |
| DESIGN PROFESSIONAL FOR THE PORTION OF |
| PERMIT FEE ATTRIBUTED TO PLAN REVIEW. |
| PLEASE SEE ATTACHED BZ #247610 |
| $2,273.80 |
| WHICH HAS NOW BEEN ADDED. PLEASE SEE |
| THIS MUST BE PAID BEFORE PLANS ARE |
| ALLOWED TO BE RE-SUBMITTED FOR NEXT |
| REVIEW. |
| **PLEASE ALSO SEE THAT ONE COPY OF EACH |
| OF THE 3 SETS OF ELECTRICAL PLANS ARE |
| NOW BEING REATINED FOR POSSIBLE REVIEW |
| BY THE FBPE'S.***** |
| |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |