Plan Review Notes For Permit 04050933 |
Permit Number |
04050933 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-10-08 00:00:00 | DENIED: | | 1.LOAD CALCULATIONS ARE TO BE IN | | ACCORDANCE WITH 2001 FBC CHAPTER 13 | | SUB-CHAPTER 600 METHOD A.CALCULATIONS | | SUBMITTED INDICATE FULL COMMERCIAL.PER | | FS 553.907, THE BUILDINGS OWNER, THE | | OWNERS ARCHITECT, OR OTHER AUTHORIZED | | AGENT LEGALLY DESIGNATED BY THE OWNER | | SHALL CERTIFY THAT THE BUILDING IS IN | | COMPLIANCE WITH THE CODE. | | | | 2.RETURN AIR TRANSFERS ARE NOT SIZED | | IN ACCORDANCE WITH 2001 FBC(M) 601.4, | | EXCEPTION 1 THROUGH 3.PLEASE SIZE THE | | FOLLOWING RETURN TRANSFERS AS FOLLOWS: | | 8" SUPPLY = 10" RETURN AIR JUMPER | | MASTER BEDROOM ALL AIR INTO THE SUITE | | SHALL BE INCLUDED. A MINIMUM OF 16" | | RETURN IS REQUIRED. | | | | 3. NON HABITABLE ROOMS LIKE THE LAUNDRY | | ROOM, ARE NOT REQUIRED TO HAVE A RETURN. |
|