Plan Review Notes
Plan Review Notes For Permit 04050933
Permit Number 04050933
Review Stop E
Sequence Number 2
Notes
Date Text
2004-09-21 00:00:00********* UNSAT 2ND REVIEW ********
  
 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN
 AS 150 MLO? NO MAIN SHOWN? 225.31 ETC.
  
 2)NOTE: PLEASE SEE LOCATION OF PANEL IS
 SHOWN IN KITCHEN WHERE COUNTERSPACE IS?
 MUST MEET 110.26
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 LOCATION AND TYOE OF SD NEAR KITCHEN.
  
 4 )NOTE: PLEASE SHOWS REQ'D DISC'S FOR
 A/C EQUIPMENT. PER 440.11
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC
 PLEASE ALSO SEE ELECTRICAL NOTES:
 MENTIONS SD'S TO BE ON WITH KIT LIGHTING
 CIRCUIT? SEE ABOVE.
  
 6)NOTE: PLEASE SEE 210.52C1 FOR RECEPTS
 ALONG KITCHEN COUNTERSPACE.
  
 7)NOTE: PLEASE SEE DINING RM RECEPT
 NOW SHOWN ON A 20A BRKR, YET STILL SHOWN
 W/ #14 AWG WHICH IS ONL RATED FOR 15A'S.
 PLEASE SEE 210.52B1
  
 8)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL. ONE SHOWS PANEL BEING A
 30 CIRCUIT, THE OTHER 40 CIRCUITS??
  
 9)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQUIRED ON TITLE BLOCK.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]