2004-07-26 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE AIC RATING MARKED IN THE PANEL IS |
| 10000, AND 22000 NOTED ON PLAN, PLEASE |
| CORRELATE. |
| |
| 2} PLEASE SHOW THE LOCATION OF THE |
| SERVICE EQUIPMENT ON THE PLAN. |
| |
| 3} THE PANEL SCHEDULE CONTAINS THE |
| FOLLOWING VIOLATIONS: |
| A) DINING ROOM CIRCUIT ON 15 AMP CKT. |
| MUST COMPLY WITH 210.52(B)(1). |
| B) THE 15 AMP SMALL APPLIANCE (KITCHEN) |
| MUST COMPLY WITH 210.11(C)(1), 20 AMP. |
| C) THE BATH CIRCUITS MUST COMPLY WITH |
| 210.11(C)(3). |
| D) THE WASHER/DRYER IS LISTED AS A |
| SINGLE UNIT BUT SHOWN AS SEPARATE |
| UNITS. PLEASE CORRELATE AND ADJUST |
| LOAD CALCULATIONS ACCORDINGLY. |
| |
| 4} THE BACK BATHROOM (WHICH DOES NOT |
| APPEAR ON THE ARCHITECTURAL PLAN A-1) |
| MUST HAVE A RECEPTACLE TO COMPLY WITH |
| 210.52(D)., ALSO CORRELATE PLANS TO |
| INDICATE IF THAT ROOM IS TO BE PART OF |
| THIS PLAN. |
| |
| 5} THE RECEPTACLE SPACING IN THE |
| DINING,AND BACK BEDROOM IS IN VIOLATION |
| OF 210.52(A)(1). |
| |
| 6} THE KITCHEN RECEPTACLES MUST COMPLY |
| WITH 210.52(C)(1) SPACING AND |
| 210.8(A)(6) GFI. |
| |
| 7} SMOKE DETECTORS ARE REQUIRED PER 8-1. |
| 4.1.6.2 NFPA-72. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |