 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE AIC RATING MARKED IN THE PANEL IS
 10000, AND 22000 NOTED ON PLAN, PLEASE
 CORRELATE.
  
 2} PLEASE SHOW THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLAN.
  
 3} THE PANEL SCHEDULE CONTAINS THE
 FOLLOWING VIOLATIONS:
 A) DINING ROOM CIRCUIT ON 15 AMP CKT.
 MUST COMPLY WITH 210.52(B)(1).
 B) THE 15 AMP SMALL APPLIANCE (KITCHEN)
 MUST COMPLY WITH 210.11(C)(1), 20 AMP.
 C) THE BATH CIRCUITS MUST COMPLY WITH
 210.11(C)(3).
 D) THE WASHER/DRYER IS LISTED AS A
 SINGLE UNIT BUT SHOWN AS SEPARATE
 UNITS. PLEASE CORRELATE AND ADJUST
 LOAD CALCULATIONS ACCORDINGLY.
  
 4} THE BACK BATHROOM (WHICH DOES NOT
 APPEAR ON THE ARCHITECTURAL PLAN A-1)
 MUST HAVE A RECEPTACLE TO COMPLY WITH
 210.52(D)., ALSO CORRELATE PLANS TO
 INDICATE IF THAT ROOM IS TO BE PART OF
 THIS PLAN.
  
 5} THE RECEPTACLE SPACING IN THE
 DINING,AND BACK BEDROOM IS IN VIOLATION
 OF 210.52(A)(1).
  
 6} THE KITCHEN RECEPTACLES MUST COMPLY
 WITH 210.52(C)(1) SPACING AND
 210.8(A)(6) GFI.
  
 7} SMOKE DETECTORS ARE REQUIRED PER 8-1.
 4.1.6.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  