Plan Review Notes For Permit 04050876 |
Permit Number |
04050876 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-21 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE NOTE, ALL PLANS DRAWN | | BY AN ARCHITECT/ENGINEER CONTAIN- | | -ING A TITLE BLOCK: MUST BE SIGNED, | | DATED AND SEALD BY THAT ARCH/ENG. | | PER FS 481.221 471.025 | | FAC 61G15-23.002, 61G1-16.004 | | | | 2} THE #2/0 CONDUCTORS ON THE RISER | | DIAGRAM DO NOT COMPLY WITH THE | | OVERCURRENT PROTECTION. PLEASE SEE | | 310.16(TABLE) 175 AMPS.THESE CONDUCTORS | | MUST BE PROTECTED PER THEIR AMPERAGE | | RATING, OR NEW CONDUCTORS INSTALLED TO | | MEET THE LOADS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|