2006-03-17 00:00:00 | *********** UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE SEC'S AND FEEDERS |
| AHVE NOW BEEN DECREASED WHICH ARE NOT |
| RATED FOR THE OCP AS SHOWNA OR THE SIZE |
| OF SERVICE. ORIG PLANS INDICATED A 200A |
| SERVICE, THEN THE REVISED PLANS IN JAN |
| 05 INDICATED A 225A SERVICE WHICH THE |
| SEC'S AND FEEDER WERE INCREASED. |
| PLEASE SEE 310.16 FOR COMMERCIAL USE |
| WHICH REQUIRES THESE CONDUCTORS TO BE |
| INCREASED. |
| 310.16,240.4, ETC |
| |
| 2) NOTE: DUE TO THE INCREASEOF SERVICE |
| ENTRANCE CONDUCTORS, THE PLANS WERE |
| REDLINED ON JAN 24,2005 TO INCREASE THE |
| GROUNDING ELECTRODE CONDUCTOR. THISWAS |
| NOT DONE AND STILL SHOWS A GROUNDING |
| ELECTRODE TOO SMALL. |
| #2 MIN).250.66, 250.50,250.52 |
| |
| 3)NOTE: PLEASE COMPLETE ALL CIRCUTING ON |
| PLANS AND CORRELATE W/ THE SUBMITTED |
| PANEL SCHEDULE. |
| PLEASE SEE 700.12E FOR EM/EXT. |
| |
| 4)NOTE: PLEASEBE SURE TO GO OVER PLANS |
| AND MAKE SURE ALL CIRCUITS CORRELATE. |
| PLEASE SEE RECEPT IN BATH ON LT CIRCUIT. |
| PLEASE SEE RECEPT ON LT CIRCUIT ON A |
| DIFFERENT FLR. |
| |
| MOST OF THE ABOVE AREAS HAVEBEEN |
| REDLINED, HOWEVER THIS IN NO WAY |
| INCLUDES ALL. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |