Plan Review Notes For Permit 04050860 |
Permit Number |
04050860 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-11-30 00:00:00 | DENIED: | | 1.RETURN AIR FROM THE CONFERENCE ROOM | | AREA IS NOT SIZED PROPERLY.R/A JUMPER | | SHALL BE A MINIMUM OF 1 1/2 TIMES THE | | SQUARE INCHES OF THE SUPPLY AIR INTO | | THAT SPACE.PLEASE INCREASE SIZE OF | | R/A | | JUMPER OR PROVIDE AN ADDITIONAL 10" R/A | | JUMPER. | | | | 2.NO DUCT SIZE INDICATED ON THE | | FOLLOWING: | | R/A JUMPER INTO THE CONFERENCE RM | | R/A JUMPER FROM THE OFFICE AREAS ON | | THE GROUND FLOOR. | | R/A DUCT FROM A/C 1 | | R/A JUMPER FROM 2ND FL PRIVATE OFFICE | | | | | | 3.RETURN AIR REQUIRED FROM THE | | SECRETARY'S OFFICE ON THE 2ND FLOOR | | ALONG WITH THE 1" DOOR UNDERCUT PER THE | | | | 2001 FBC(M)601.4 EXCEPTION 1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|