Plan Review Notes
Plan Review Notes For Permit 04050860
Permit Number 04050860
Review Stop E
Sequence Number 3
Notes
Date Text
2004-11-17 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE THERE ARE NUMEROUS
 ITEMS ON PANEL SCHEDULE WHICH HAVE BEEN
 ADDED OR LOADS INCREASE YET, LOAD HAS
 GONE DOWN FROM PREVIOUS PLANS?? HOW IS
 THIS POSSIBLE?
 PLEASE SEE INCREASED A/C LOAD.
 PLEASE SEE ADDED RECEPT LOAD/LT, GARBAGE
 DISP ETC.
  
 2)NOTE: PLEASE ALSO SEE LOADING OF SOME
 RECEPT CIRCUITS. 1920 W MAX ON A 20A
 BRANCH CIRCUIT.
 PLEASE SEE 220.13 FOR 180VA FOR EACH
 RECEPT.
 SEE #22,24,,,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
  
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]