Plan Review Notes
Plan Review Notes For Permit 04050860
Permit Number 04050860
Review Stop M
Sequence Number 2
Notes
Date Text
2004-07-21 00:00:00PROVISO:
 1.DUCT SMOKE DETECTORS TO BE INSTALLED
 IN THE SUPPLY AIR DUCT & NOT THE RETURN
 AS INDICATED.2001 FBC(M) 606.2.1.
  
 2.RETURN AIR REQUIRED FROM THE 2ND
 FLOOR SECRETARY'S OFFICE & THE 1ST FLOOR
 CONFERENCE ROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.