Plan Review Notes
Plan Review Notes For Permit 04050860
Permit Number 04050860
Review Stop B
Sequence Number 2
Notes
Date Text
2004-07-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #12, FBC
 1006.2.4 "EXTERIOR STAIRS SHALL BE
 SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR . . ."
 FIRE RESISTANCE RATING FOR THE EXISTING
 WALLS WAS NOT CLEAR FROM THE PLAN.
 THE ENERGY CALCS SPECIFY FRAME EXTERIOR
 WALLS WITH A 24" SPACING; FBC TABLE
 709.6.2B ASSIGNS FIRE RESISTANCE TO
 FRAME WALLS WITH 16" SPACING ONLY.
 PROVIDE EITHER CALCULATED FIRE
 RESISTANCE RATING CHAPTER 7 OR ASSEMBLY
 LISTING.
  
 2.)THE INFILL DETAIL ALSO DOES NOT
 DEMONSTRATE COMPLIANCE.1 HR REQUIRED.
  
 3.)SEE PREVIOUS LIST, ITEM #13.
 ALTHOUGH IT IS CLEAR THAT THE STAIR IS
 OPEN, THE USABLE STILL UNDER THE STAIR
 STILL MUST COMPLY (1 HR). NONCOMBUSTIBLE
 MATERIALS DOES NOT COMPLY; USE OF
 NONCOMBUSTIBLE MATERIALS DO NOT
 CONSTITUTE A 1 HR ASSEMBLY.ALSO, YOU
 ARE STATING THAT THIS IS NONCOMBUSTIBLE;
 ISN'T THE ROOF FRAMING WOOD?SHEATHING?
  
 4.)THE FILE ROOM DOOR APPEARS TO ALSO
 BE WITHIN 10' OF THE STAIR.SHOW AS
 A PROTECTED OPENING ON THE PLAN, SUBMIT
 PRODUCT APPROVAL AND FIRE RATING
 INFORMATION FOR THIS EXTERIOR OPENING.
  
 5.)THE PREVIOUS LIST INCLUDED
 CORRECTIONS IN REGARDS TO THE RAMP
 (ITEMS 8 AND 9).THIS INDICATES THAT
 IT WAS NOT CODE COMPLIANT ON THE
 ORIGINAL SET OF PLANS, AND ARE CODE
 COMPLIANT ON THE REVISED SET OF PLANS,
 BUT IS NOT CLOUDED.PLEASE ALWAYS
 CLEARLY INDICATE ALL CHANGES AND SUBMIT
 OLD SHEETS.
  
 6.)REVISE THE SITE PLAN TO REFLECT
 CHANGES MADE TO THE RAMP.
  
 7.)SEPARATE PERMITS REQUIRED.
  
 8.)LOUNGE SINK DOES NOT SHOW
 COMPLIANCE WITH FBC11-4.24.3, 11-4.24.4.
  
 9.)IN REGARDS TO THE AFFIDAVIT FOR THE
 FLOORS, PLEASE REVISE TO CLEARLY
 INDICATE THAT BOTH OF THE FLOORS (1ST
 AND 2ND FLOOR) ARE INCLUDED IN THIS
 AFFIDAVIT (STATES "FLOOR SYSTEM"; WHICH
 ONE?BOTH MUST BE CERTIFIED.)ALSO
 BE ADVISED THAT YOU ARE CERTIFYING THE
 FLOORS BASED ON AN INSPECTION PERFORMED
 BY A PERSON NOT LICENSED TO DO DESIGN
 OR TO MAKE STRUCTURAL DETERMINATIONS.
 PLEASE STATE THE LOADS WHICH IN THE
 LETTER ARE REFERRED TO BY CODE SECTION.
 SUBMIT TWO COPIES; REQUIRED TO BE
 SEALED AND INCLUDE A TITLE BLOCK.
  
 10.) SEE PREVIOUS LIST, ITEM 19, THE
 INTERIOR STAIRS ALSO ARE REQUIRED TO
 HAVE A HANDRAIL ON BOTH SIDES.
  
 11.) IN REGARDS TO THE PREVIOUS LIST,
 ITEM #22 WAS A TYPO; SHOULD READ "TO
 COMPLY WITH FBC1804.6.3.1."PLEASE
 ADDRESS AT THIS TIME.
  
 12.)SEE PREVIOUS LIST, ITEM #20.
 THIS IS AN AREA WHERE SOILS ARE
 REQUIRED.ALTHOUGH YOU STATE THAT THE
 FOUNDATION WORK IS MINIMAL, SOILS ARE
 STILL REQUIRED AS FOUNDATION WORK IS
 BEING PERFORMED.
  
 13.)TEST REPORTS FOR THE GAF RUBBEROID
 WERE NOT SUBMITTED, BUT FLORIDA STATE
 PRODUCT APPROVALS WERE SUBMITTED. PLEASE
 PROVIDE TWO COPIES OF THE TEST REPORT.
  
 14.) PROVIDE STATE PAS AND TEST REPORTS
 FOR THE PGT FIXED GLASS WINDOW.
  
 15.) SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).