2004-06-05 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| |
| |
| 1) SHT 1 OF 5 GROUND FLOOR PLAN. LOUNGE |
| SINK SHALL COMPLY WITH 11-4.24 AND ALL |
| SUBSECTIONS. SHOW TURNING AREA SEE FIGS |
| 3A & 3B. SECTION 11-4.2.3 & 11-4.2.4.2 |
| 2) SHT 1 OF 5 GROUND FLOOR PLAN. TOILET |
| ROOM - SHOW CLEAR FLOOR SPACE FOR LAV & |
| W/C. SHOW TURNING AREA PER SECTION 11-4. |
| 22.3. |
| 3) SHT 1 OF 5 DOORS SHALL NOT SWING INTO |
| THE CLEAR FLOOR SPACE FOR ANY FIXTURE. |
| SEE TOILET ROOM DOOR. SECTION 11-4.22.2 |
| 4) PER TABLE 403.1 A DRINKING FOUNTAIN |
| IS REQUIRED. ALSO SEE SECTION 410.1. |
| 5) SHOW LOCATION OF WATER HEATER ON THE |
| FLOOR PLAN. SECTION 104.2.1 |
| 6) SUBMIT A WATER RISER DIAGRAM. SECTION |
| 104.3.1.1 - SHOW LOCATION OF WATER HAMM- |
| ER ARRESTORS PER PDI-WH 201. |
| 7) SHT 5 OF 5 UNDER PLUMBING NOTES THERE |
| ARE GAS NOTES. A SEPARATE GAS PERMIT IS |
| REQUIRED IF THERE IS GAS BEING INSTALLED |
| SEPARATE GAS PLANS REQUIRED ALSO. SECT- |
| ION 104.3.1.1 |
| 8) SEE ELECTRICAL REVIEW CONCERNING THE |
| SIGNATURE OF THE ARCHITECT, AND REMOVAL |
| OF OLD SHEETS WHEN RESUBMITTING PLANS. |
| |