Plan Review Notes
Plan Review Notes For Permit 04050860
Permit Number 04050860
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
  
 1) SHT 1 OF 5 GROUND FLOOR PLAN. LOUNGE
 SINK SHALL COMPLY WITH 11-4.24 AND ALL
 SUBSECTIONS. SHOW TURNING AREA SEE FIGS
 3A & 3B. SECTION 11-4.2.3 & 11-4.2.4.2
 2) SHT 1 OF 5 GROUND FLOOR PLAN. TOILET
 ROOM - SHOW CLEAR FLOOR SPACE FOR LAV &
 W/C. SHOW TURNING AREA PER SECTION 11-4.
 22.3.
 3) SHT 1 OF 5 DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR ANY FIXTURE.
 SEE TOILET ROOM DOOR. SECTION 11-4.22.2
 4) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1.
 5) SHOW LOCATION OF WATER HEATER ON THE
 FLOOR PLAN. SECTION 104.2.1
 6) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.3.1.1 - SHOW LOCATION OF WATER HAMM-
 ER ARRESTORS PER PDI-WH 201.
 7) SHT 5 OF 5 UNDER PLUMBING NOTES THERE
 ARE GAS NOTES. A SEPARATE GAS PERMIT IS
 REQUIRED IF THERE IS GAS BEING INSTALLED
 SEPARATE GAS PLANS REQUIRED ALSO. SECT-
 ION 104.3.1.1
 8) SEE ELECTRICAL REVIEW CONCERNING THE
 SIGNATURE OF THE ARCHITECT, AND REMOVAL
 OF OLD SHEETS WHEN RESUBMITTING PLANS.
  