Plan Review Notes For Permit 04050860 |
Permit Number |
04050860 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-20 00:00:00 | 1) ALL NEW STAIRS AND RAMPS SHALL HAVE | | HANDRAILS ON BOTH SIDES. | | | | 2) BUILDING ADDRESS IS REQUIRED. A | | MINIMUM OF 6" HIGH NUMBERS ARE | | REQUIRED. | | | | 3) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | 4) NO INFORMATION PROVIDED ABOUT | | PORTABLE FIRE EXTINGUISHERS. | | | | 5) PLEASE EXPLAIN EXITING RATIONALE | | FROM SECOND FLOOR. ALSO PLEASE IDENTIFY | | ALL OPENINGS WITHIN 10 FEET OF THE | | STAIRS BOTH VERTICALLY AND HORIZONTALLY. | | | | 6) PLEASE INDICATE TOTAL OCCUPANT LOAD | | FOR BOTH THE FIRST AND SECOND FLOOR. | | | | 7) HOW WILL THE NEW PRE-FAB STAIRS BE | | SLIP RESISTANT. | | | | 8) PLEASE INDICATE PRESCRIPTIVE | | STRENGTH REQUIREMENTS FOR HANDRAILS | | AND GUARDRAILS. | | | | 9) NO EMERGENCY LIGHTS OR EXIT SIGNS | | SHOWN ON SECOND FLOOR POWER PLAN. | | PLEASE REVISE AS NECESSARY. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|