Plan Review Notes
Plan Review Notes For Permit 04050860
Permit Number 04050860
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-20 00:00:001) ALL NEW STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 2) BUILDING ADDRESS IS REQUIRED. A
 MINIMUM OF 6" HIGH NUMBERS ARE
 REQUIRED.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 4) NO INFORMATION PROVIDED ABOUT
 PORTABLE FIRE EXTINGUISHERS.
  
 5) PLEASE EXPLAIN EXITING RATIONALE
 FROM SECOND FLOOR. ALSO PLEASE IDENTIFY
 ALL OPENINGS WITHIN 10 FEET OF THE
 STAIRS BOTH VERTICALLY AND HORIZONTALLY.
  
 6) PLEASE INDICATE TOTAL OCCUPANT LOAD
 FOR BOTH THE FIRST AND SECOND FLOOR.
  
 7) HOW WILL THE NEW PRE-FAB STAIRS BE
 SLIP RESISTANT.
  
 8) PLEASE INDICATE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS
 AND GUARDRAILS.
  
 9) NO EMERGENCY LIGHTS OR EXIT SIGNS
 SHOWN ON SECOND FLOOR POWER PLAN.
 PLEASE REVISE AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910