Plan Review Notes
Plan Review Notes For Permit 04050860
Permit Number 04050860
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-28 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE BLDG IS SHOWN AS A
 CHANGE OF OCCUPANCY FROM RESIDENCE TO
 COMMERCIAL OFFICE BLDG.
 PLEASE ADJUST PLANS ACCORD.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE SEE NEC 220 FOR LOAD
 PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/ EXT LTS.
 PLEASE SEE FIRE REVIEW COMMENTS FOR
 EM/EXT LTS.
  
 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU'S
 DO NOT SEEM TO CORRELATE TO NEC 424.3B
 PLEASE VERIFY KW LOAD AND OCP.
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.122,250.24
  
 7)NOTE: PLEASE CORRELATE RISER WITH
 PANEL, ONE SHOWS PANEL BEING MCB, OTHER
 SHOWS MLO??
  
 8)NOTE: PLEASE SEE SEC'S SHOWN AS 1/0'S
 PLEASE SEE 310.16 FOR MIN SEC'S FOR A
 200A SERVICE.
  
 9)NOTE: PLEASE SEE 210.70/210.63 FOR
 AHU WHICH APPEARS TO BE IN AN ATTIC??
  
 10)NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES A SIGNATURE FOR ARCH.
 PLEASE SEE THAT PLANS APPEAR TO AN
 INITIAL FOR FIRST NAME.
 IF THIS IS LEGAL "SIGNATURE", PLEASE
 PROVIDE A SIGNED, DATED AND SEALED
 NOTARIZED LETTER STATING THIS IS LEGAL
 SIGNATURE. WE CAN THEN PLACE THIS IN
 A SIGNATURE FILE FOR FUTURE REFERENCE
 DUE TO ISSUES WE HAVE ENCOUNTERED WITH
 MORE THAN ONE "SIGNATURE" FOR INDIVIDUAL
 'S ON PLANS BEING SUBMITTED TO CITY OF
 WEST PALM BEACH. WE ARE REQUIRING
 "SIGNATURE" VERIFICATION FOR FILE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 INCLUDING IMPACT FEES FOR PALM BEACH
 COUNTY.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO SETS FOR
 REVIEW AND STAMPING. ONE SET OF OLD
 SHEETS MAY BE SUBMITTED FOR REFERENCE
 FOR SOME REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]