2004-05-28 00:00:00 | ************* UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE BLDG IS SHOWN AS A |
| CHANGE OF OCCUPANCY FROM RESIDENCE TO |
| COMMERCIAL OFFICE BLDG. |
| PLEASE ADJUST PLANS ACCORD. |
| |
| 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. |
| |
| 3)NOTE: PLEASE SEE NEC 220 FOR LOAD |
| PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 4)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| -ING OF EM/ EXT LTS. |
| PLEASE SEE FIRE REVIEW COMMENTS FOR |
| EM/EXT LTS. |
| |
| 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU'S |
| DO NOT SEEM TO CORRELATE TO NEC 424.3B |
| PLEASE VERIFY KW LOAD AND OCP. |
| |
| 6)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN TO PANEL. |
| 250.110,250.122,250.24 |
| |
| 7)NOTE: PLEASE CORRELATE RISER WITH |
| PANEL, ONE SHOWS PANEL BEING MCB, OTHER |
| SHOWS MLO?? |
| |
| 8)NOTE: PLEASE SEE SEC'S SHOWN AS 1/0'S |
| PLEASE SEE 310.16 FOR MIN SEC'S FOR A |
| 200A SERVICE. |
| |
| 9)NOTE: PLEASE SEE 210.70/210.63 FOR |
| AHU WHICH APPEARS TO BE IN AN ATTIC?? |
| |
| 10)NOTE: PLEASE SEE FS 481.221 WHICH |
| REQUIRES A SIGNATURE FOR ARCH. |
| PLEASE SEE THAT PLANS APPEAR TO AN |
| INITIAL FOR FIRST NAME. |
| IF THIS IS LEGAL "SIGNATURE", PLEASE |
| PROVIDE A SIGNED, DATED AND SEALED |
| NOTARIZED LETTER STATING THIS IS LEGAL |
| SIGNATURE. WE CAN THEN PLACE THIS IN |
| A SIGNATURE FILE FOR FUTURE REFERENCE |
| DUE TO ISSUES WE HAVE ENCOUNTERED WITH |
| MORE THAN ONE "SIGNATURE" FOR INDIVIDUAL |
| 'S ON PLANS BEING SUBMITTED TO CITY OF |
| WEST PALM BEACH. WE ARE REQUIRING |
| "SIGNATURE" VERIFICATION FOR FILE. |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| INCLUDING IMPACT FEES FOR PALM BEACH |
| COUNTY. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO SETS FOR |
| REVIEW AND STAMPING. ONE SET OF OLD |
| SHEETS MAY BE SUBMITTED FOR REFERENCE |
| FOR SOME REVIEWS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |