Plan Review Notes For Permit 04050853 |
Permit Number |
04050853 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-09 00:00:00 | DENIED: | | 1.CERTIFICATE OF AUTHORIZATION # ON | | THE TITLE BLOCK IS NOT CORRECT ACCORDING | | TO DBPR.PLEASE CORRECT. | | | | 2.PLAN SHEET M2.1 INDICATES EXHAUST | | AIR FROM EF-1 DISCHARGING INTO THE | | PLENUM.PER 2001 FBC(M) 501.3, EVERY | | MECHANICAL EXHAUST SYSTEM SHALL BE | | DISCHARGED TO THE OUTDOORS WHERE IT | | CANNOT BE DRAWN IN BY A VENTILATING | | SYSTEM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|