2005-02-01 00:00:00 | ************** UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE AN EQUIPMENT |
| GROUNDING CONDUCTOR IS SHOWN FROM METER |
| TO MAIN/PANEL "B". PLEASE SEE |
| 250.6,250.24. EQP GRND IS ONLY INSTALLED |
| AFTER THE FIRST MEANS OF DISC. |
| |
| 2)NOTE: PLEASE SEE |
| 210.11C1,210.52B,220.16, SMALL APPL IS |
| 1.5 KW MIN, PLEASE ALSO SEE DINING RM |
| RQ'D RECEPTS. |
| |
| 3)NOTE: PLEASE SEE 5KW SHOWN ON 1P20A |
| BRKR FOR GOLF CART CHARGER. |
| PLEASE SEE 3KW ON 1P20A BATH GFI |
| CIRCUIT. |
| PLEASE ADJUST. |
| LOADS EXCEED RATINGS OF CIRCUITS. |
| 240.4 ETC. |
| |
| 4)NOTE:PLEASE SEE MAIN BRKR PANEL "B", |
| IS SHOWN AS 8-16 CIRCUIT PANEL YET, |
| PANEL "B" IS SHOWN ASA 42 CIRCUIT |
| PANEL ON PANEL SCHEDULE. |
| |
| 5)NOTE: PLEASE SHOW PANEL "C" ON PLANS. |
| COULD NOT LOCATE THIS ON PLANS. |
| |
| |
| 6 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |