2004-05-19 00:00:00 | *************** UNSAT ************** |
| |
| 1)NOTE: PLEAS INDICATE GFI/GFI PROTECT- |
| -ION JACUZZI TUB. 680 |
| |
| 2)NOTE: PLEASE SEE AN EQUIPMENT GROUND- |
| -ING CONDUCTOR IS SHOWN FROM METER TO |
| DISC "B". PLEASE SEE 250.6/250.24 |
| |
| 3)NOTE: PLEASE SEE 210.52C1 FOR MISSING |
| RECEPTS ON KITCHEN COUNTERSPACE. |
| |
| 4)NOTE: PLEASE SEE 210.63 FOR MISSING |
| GFI RECEPT FOR A/C COND UNITS. |
| |
| 5)NOTE: PLEASE SEE SEE RAISED SEAL MUST |
| BE CLEAR AND VISABLE WITH ALL INFORMAT- |
| -ION. PLEASE ALSO SEE FS 481.221, WHICH |
| REQ'S A COMPLETE SIGNATURE. FIRST NAME |
| IS SHOWN AS AN INITIAL. PLEASE ALSO |
| SIGN FIRST NAME. PER DBPR. |
| THIS IS REQ'D ON ALL PLANS WEATHER OR |
| NOT COMMENT IS MADE BY OTHER REVIEWERS. |
| |
| 6 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 7)NOTE: PLEASE SEE ONE PANEL IS SHOWN |
| IN GARAGE, PLEASE INDICATE LOCATION OF |
| OTHER PANEL. |
| |
| 8)NOTE: PLEASE SEE SD IS REQ'D TO BE |
| MOVED INTO MASTER BEDRM. NFPA-72 |
| 8-1 |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |