2004-06-07 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE BUILDING IS A TYPE II, FULLY |
| SPRINKLED.THIS STRUCTURE IS |
| CONSIDERED A PART OF THE PRIMARY |
| BUILDING SO MUST ALSO BE TYPE II, |
| FULLY SPRINKLED.SHOW COMPLIANCE. |
| |
| 2.)THE ELEVATIONS INDICATE "INFILL |
| BY OTHERS".CALCULATIONS WERE |
| PROVIDED USING A .18 COEFFICIENT FOR |
| ENCLOSED BUILDINGS.EITHER PROVIDE |
| INFORMATION ABOUT THE INFILL TO MAKE |
| THIS AN ENCLOSED BUILDING OR PROVIDE |
| NEW CALCULATIONS.TEST REPORTS REQUIRED |
| FOR THE SLIDING GLASS DOORS, LOUVERS, |
| IMPACT PROTECTION, SWING DOORS. |
| |
| 3.)PROVIDE THE INFORMATION REQUIRED |
| TO BE ON PLANS FBC1606.1.7 2003 |
| AMENDMENT.MOST OF THE INFORMATION HAS |
| BEEN PROVIDED BUT THE ENCLOSURE |
| CLASSIFICATION IS MISSING. |
| |
| 4.)PROVIDE THE ENGINEER'S INFORMATION |
| ON THE PLANS (TITLE BLOCK) AS PER |
| FAC61G15-23.002 (ADDRESS). |
| |
| 5.)PROVIDE PRODUCT APPROVALS FOR ALL |
| STRUCTURAL COMPONENTS AS PER RULE 9B72. |
| WWW.FLORIDABUILDING.ORG FOR MORE |
| INFORMATION. |