Plan Review Notes
Plan Review Notes For Permit 04050493
Permit Number 04050493
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE BUILDING IS A TYPE II, FULLY
 SPRINKLED.THIS STRUCTURE IS
 CONSIDERED A PART OF THE PRIMARY
 BUILDING SO MUST ALSO BE TYPE II,
 FULLY SPRINKLED.SHOW COMPLIANCE.
  
 2.)THE ELEVATIONS INDICATE "INFILL
 BY OTHERS".CALCULATIONS WERE
 PROVIDED USING A .18 COEFFICIENT FOR
 ENCLOSED BUILDINGS.EITHER PROVIDE
 INFORMATION ABOUT THE INFILL TO MAKE
 THIS AN ENCLOSED BUILDING OR PROVIDE
 NEW CALCULATIONS.TEST REPORTS REQUIRED
 FOR THE SLIDING GLASS DOORS, LOUVERS,
 IMPACT PROTECTION, SWING DOORS.
  
 3.)PROVIDE THE INFORMATION REQUIRED
 TO BE ON PLANS FBC1606.1.7 2003
 AMENDMENT.MOST OF THE INFORMATION HAS
 BEEN PROVIDED BUT THE ENCLOSURE
 CLASSIFICATION IS MISSING.
  
 4.)PROVIDE THE ENGINEER'S INFORMATION
 ON THE PLANS (TITLE BLOCK) AS PER
 FAC61G15-23.002 (ADDRESS).
  
 5.)PROVIDE PRODUCT APPROVALS FOR ALL
 STRUCTURAL COMPONENTS AS PER RULE 9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.