Plan Review Notes For Permit 04050413 |
Permit Number |
04050413 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | FBC-2001 CHAPTER 1 | | | | 1) MORE INFORMATION REQUIRED ON FOUNTAIN | | PIPING DIAGRAM SHOWS 1" PIPE FOR FOUNT- | | AIN. IS THIS AN EXISTING FOUNTAIN? OR | | IS THE FOUNTAIN BEING BUILT AT THIS TIME | | IF NEW FOUNTAIN A DETAIL WILL BE REQUIR- | | ED, AND VALUATION WILL HAVE TO INCLUDE | | THE FOUNTAIN. | | 2) PROPOSAL INDICATES 1-SPA RETURN. THIS | | IS NOT SHOWN ON THE PIPING DIAGRAM. | | PLEASE CLARIFY. | | 3) VENT PIPE FOR SPA MAIN DRAINS IS NOT | | SHOWN ON PIPING DIAGRAM. SHOW ALL PIPING | | 4) EXTERNAL HARTFORD LOOP REQUIRED FOR | | HEAT PUMP TO MAINTAIN WATER RETENTION | | PER 424.2.14.2. INDICATE ON PLANS. | | 5) BACKFLOW PREVENTOR SHALL BE INSTALLED | | PRIOR TO COMMENCING WORK ON SPA. (INDIC- | | ATE IF INSTALLED WITH POOL). | | 6) NEW VALUATION PER SECTION 104.6.5 | | AND MARSHALL AND SWIFT WILL BE $10,137. | | FEES DUE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|