Plan Review Notes
Plan Review Notes For Permit 04050413
Permit Number 04050413
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) MORE INFORMATION REQUIRED ON FOUNTAIN
 PIPING DIAGRAM SHOWS 1" PIPE FOR FOUNT-
 AIN. IS THIS AN EXISTING FOUNTAIN? OR
 IS THE FOUNTAIN BEING BUILT AT THIS TIME
 IF NEW FOUNTAIN A DETAIL WILL BE REQUIR-
 ED, AND VALUATION WILL HAVE TO INCLUDE
 THE FOUNTAIN.
 2) PROPOSAL INDICATES 1-SPA RETURN. THIS
 IS NOT SHOWN ON THE PIPING DIAGRAM.
 PLEASE CLARIFY.
 3) VENT PIPE FOR SPA MAIN DRAINS IS NOT
 SHOWN ON PIPING DIAGRAM. SHOW ALL PIPING
 4) EXTERNAL HARTFORD LOOP REQUIRED FOR
 HEAT PUMP TO MAINTAIN WATER RETENTION
 PER 424.2.14.2. INDICATE ON PLANS.
 5) BACKFLOW PREVENTOR SHALL BE INSTALLED
 PRIOR TO COMMENCING WORK ON SPA. (INDIC-
 ATE IF INSTALLED WITH POOL).
 6) NEW VALUATION PER SECTION 104.6.5
 AND MARSHALL AND SWIFT WILL BE $10,137.
 FEES DUE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]