Plan Review Notes
Plan Review Notes For Permit 04050411
Permit Number 04050411
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) 1-1/2" ATMOSPHERIC VENT LENGTH TABLE
 (3 SECOND RELEASE) ONLY GOES UP TO 2 HP
 PUMP. PUMP IN POOL SPECIFICATION SHEET
 IS CALLED OUT AS A 2-1/2 HP PUMP. PLEASE
 SHOW MAXIMUM LENGTH FOR THIS SIZE PUMP.
 SECTION 104.2.1
 2) INFORMATIONAL: BACKFLOW SHALL BE IN-
 STALLED PRIOR TO COMMENCING WORK ON THE
 POOL.
 3) VALUATION PER MARSHALL AND SWIFT PER
 SECTION 104.6.5 SHALL BE $45,718. FEES
 DUE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]