Plan Review Notes For Permit 04050400
Permit Number 04050400
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-14 00:00:001) WHAT IS PLANNED TO BE STORED IN THE
 WAREHOUSE. ARE ANY FLAMMABLE OR
 COMBUSTIBLE LIQUIDS, SOLIDS, OR GASES
 PLANNED. PLEASE PROVIDE INFORMATION.
  
 2) WHY IS THERE NO FIRE SEPARATION
 PLANNED BETWEEN THE WAREHOUSE AND THE
 OFFICE AREA. NFPA 101, THE LIFE SAFETY
 CODE, 2000 EDITION, SECTION 8-4.1.1
 REQUIES THAT "PROTECTION FROM ANY
 AREA HAVING A DEGREE OF HAZARD GREATER
 THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE
 SHALL BE PROVIDED BY ONE OF THE
 FOLLOWING MEANS:
 A) ENCLOSE THE AREA WITH A FIRE BARRIER
 WITHOUT WINDOWS THAT HAS A 1 HOUR
 FIRE RESISTANCE RATING IN ACCORDANCE
 WITH SECTION 8.2.
 B) PROTECT THE AREA WITH AUTOMATIC
 EXTINGUISHING SYSTEMS IN ACCORDANCE
 WITH SECTION 9.7
 C) APPLY BOTH 8.4.1.1(1) AND (2) WHERE
 THE HAZARD IS SEVERE OR WHERE OTHERWISE
 SPECIFIED BY CHAPTERS 12-42".
 THE APPENDIX FURTHER EXPLAINS "AREAS
 REQUIRING SPECIAL HAZARD PROTECTION
 INCLUDE, BUT ARE NOT LIMITED TO, AREAS
 SUCH AS THOSE USED FOR STORAGE OF
 COMBUSTIBLES OR FLAMMABLES, AREAS
 HOUSING HEAT PRODUCING APPLIANCES,
 OR AREAS USED FOR MAINTENANCE PURPOSES.
  
 3) ANOTHER EXIT SIGN IS NEEDED TO
 DIRECT PERSONS FROM THE WAREHOUSE
 AREA INTO THE OFFICE AREA.
  
 4) NO PORTABLE FIRE EXTINGUISHERS SHOWN
 ON THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910