2004-05-14 00:00:00 | 1) WHAT IS PLANNED TO BE STORED IN THE |
| WAREHOUSE. ARE ANY FLAMMABLE OR |
| COMBUSTIBLE LIQUIDS, SOLIDS, OR GASES |
| PLANNED. PLEASE PROVIDE INFORMATION. |
| |
| 2) WHY IS THERE NO FIRE SEPARATION |
| PLANNED BETWEEN THE WAREHOUSE AND THE |
| OFFICE AREA. NFPA 101, THE LIFE SAFETY |
| CODE, 2000 EDITION, SECTION 8-4.1.1 |
| REQUIES THAT "PROTECTION FROM ANY |
| AREA HAVING A DEGREE OF HAZARD GREATER |
| THAN THAT NORMAL TO THE GENERAL |
| OCCUPANCY OF THE BUILDING OR STRUCTURE |
| SHALL BE PROVIDED BY ONE OF THE |
| FOLLOWING MEANS: |
| A) ENCLOSE THE AREA WITH A FIRE BARRIER |
| WITHOUT WINDOWS THAT HAS A 1 HOUR |
| FIRE RESISTANCE RATING IN ACCORDANCE |
| WITH SECTION 8.2. |
| B) PROTECT THE AREA WITH AUTOMATIC |
| EXTINGUISHING SYSTEMS IN ACCORDANCE |
| WITH SECTION 9.7 |
| C) APPLY BOTH 8.4.1.1(1) AND (2) WHERE |
| THE HAZARD IS SEVERE OR WHERE OTHERWISE |
| SPECIFIED BY CHAPTERS 12-42". |
| THE APPENDIX FURTHER EXPLAINS "AREAS |
| REQUIRING SPECIAL HAZARD PROTECTION |
| INCLUDE, BUT ARE NOT LIMITED TO, AREAS |
| SUCH AS THOSE USED FOR STORAGE OF |
| COMBUSTIBLES OR FLAMMABLES, AREAS |
| HOUSING HEAT PRODUCING APPLIANCES, |
| OR AREAS USED FOR MAINTENANCE PURPOSES. |
| |
| 3) ANOTHER EXIT SIGN IS NEEDED TO |
| DIRECT PERSONS FROM THE WAREHOUSE |
| AREA INTO THE OFFICE AREA. |
| |
| 4) NO PORTABLE FIRE EXTINGUISHERS SHOWN |
| ON THE PLANS. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |