Plan Review Notes For Permit 04050394 |
Permit Number |
04050394 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-01-25 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} WALL COUNTER SPACES. A RECEPTACLE | | OUTLET SHALL BE INSTALLED AT EACH WALL | | COUNTER SPACE THAT IS 300 MM (12 IN.) OR | | WIDER. RECEPTACLE OUTLETS SHALL BE | | INSTALLED SO THAT NO POINT ALONG THE | | WALL LINE IS MORE THAN 600 MM (24 IN.) | | MEASURED HORIZONTALLY FROM A RECEPTACLE | | OUTLET IN THAT SPACE. | | | | 2} SMOKE DETECTORS PER 8-1.4.1.6 | | NFPA-72. | | | | 3} OUTDOOR OUTLETS. FOR A ONE-FAMILY | | DWELLING AND EACH UNIT OF A TWO-FAMILY | | DWELLING THAT IS AT GRADE LEVEL, AT | | LEAST ONE RECEPTACLE OUTLET ACCESSIBLE | | AT GRADE LEVEL AND NOT MORE THAN 2.0 M | | (61/2 FT) ABOVE GRADE SHALL BE INSTALLED | | AT THE FRONT AND BACK OF THE DWELLING. | | SEE 210.8(A)(3). | | | | NONE OF THESE REDLINED ITEMS WERE | | CORRECTED ON THE REVISIONS.PLEASE | | CORRECT SAME AND RESUBMIT FOR REVIEW. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|