2004-05-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SDHT A-2 SANITARY RISER DIAGRAM, THE
 WASH MACHINE IS NOT VENTED, REQUIRES A
 STANDPIPE AND REQUIRES A CLEANOUT 4'
 ABOVE THE FLOOR PER SECTIONS 901.2.1,
 1002.1, 802.4, & 708.10. (SEE RED LINES
 ON RISER DIAGRAM). - SIZE ALL PIPES ON
 RISER PER TABLE 709.1.
 2) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 PER DBPR, INITIALS ARE NOT ACCEPTABLE.
 IF THIS YOUR LEAGAL SIGNATURE, A SIGNED,
 SEALED, DATED LETTER WITH TITLE BLOCK
 STATING SUCH WITH A COPY OF LICENSE
 SHOWING SIGNATURE CAN BE SUBMITTED FOR
 OUR FILE. LETTER SHALL BE NOTORIZED.
 FAC 61G1-16.003 & FS 481.221
 3) LICENSE NUMBER REQUIRED ON TITLE
 BLOCK PER FAC 61G1-16.004 & FS 481.2055.
 4) SHT A-1 PLUMBING NOTES: CODE IN
 EFFECT AT THIS TIME IS FBC-2001 NOT THE
 SOUTHERN BUILDING CONGRESS CODE AS IN-
 DICATED. PLEASE CHANGE CODE REFERENCE.
  