Plan Review Notes For Permit 04050352 |
Permit Number |
04050352 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) SDHT A-2 SANITARY RISER DIAGRAM, THE | | WASH MACHINE IS NOT VENTED, REQUIRES A | | STANDPIPE AND REQUIRES A CLEANOUT 4' | | ABOVE THE FLOOR PER SECTIONS 901.2.1, | | 1002.1, 802.4, & 708.10. (SEE RED LINES | | ON RISER DIAGRAM). - SIZE ALL PIPES ON | | RISER PER TABLE 709.1. | | 2) THE PERSONAL SIGNATURE OF THE ARCHIT- | | ECT SHALL APPEAR ON ALL ARCHITECTURAL | | DOCUMENTS TO BE FILED FOR PUBLIC RECORD. | | PER DBPR, INITIALS ARE NOT ACCEPTABLE. | | IF THIS YOUR LEAGAL SIGNATURE, A SIGNED, | | SEALED, DATED LETTER WITH TITLE BLOCK | | STATING SUCH WITH A COPY OF LICENSE | | SHOWING SIGNATURE CAN BE SUBMITTED FOR | | OUR FILE. LETTER SHALL BE NOTORIZED. | | FAC 61G1-16.003 & FS 481.221 | | 3) LICENSE NUMBER REQUIRED ON TITLE | | BLOCK PER FAC 61G1-16.004 & FS 481.2055. | | 4) SHT A-1 PLUMBING NOTES: CODE IN | | EFFECT AT THIS TIME IS FBC-2001 NOT THE | | SOUTHERN BUILDING CONGRESS CODE AS IN- | | DICATED. PLEASE CHANGE CODE REFERENCE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|