2004-06-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) COMPLY WITH FBC-2001 SEC 424.2 |
| PRIVATE SWIMMING POOLS. (ADD TO NOTES) |
| 2) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-5. (ADD TO NOTES) |
| 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. (DETAIL) |
| 4) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| MENT AVOIDANCE. (DETAIL) |
| 5) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. |
| 6) FBC-2001424.2.7.1 POOL CIRCULATING |
| PUMPS SHALL BE EQUIPPED ON THE INLET |
| SIDE WITH AN APPROVED TYPE HAIR AND LINT |
| STRAINER WHEN USED WITH A PRESSURE FIL- |
| TER. (DETAIL OR ADD TO NOTES) |
| 7) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 8) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 9) FBC-2001 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 10) FBC-2001 424.2.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL) |
| 11) FBC-2001 424.2.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN THE HEATER WHEN PUMP IS SHUT |
| OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| 12) FBC-2001 424.2.14.4 CONNECTIONS, ALL |
| WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| LED WITH FLANGES OR UNION CONNECTIONS |
| ADJACENT TO THE HEATER. (ADD TO NOTES) |
| 13) FBC02001 424.2.15 GAS PIPING SHALL |
| COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| AND PERMIT REQUIRED. |
| 14) SUBMIT 2 SETS OF PLANS FOR REVIEW |
| PER SECTION 104.2.1. |
| 3)ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| SHEET. IF PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME AND LICENSE NUMBER, AS WELL |
| AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING |
| BUSINESS ON EACH SHEET. A TITLE BLOCK |
| WILL SATISFY THIS REQUIREMENT. FAC |
| 61G15-23.002(2) - FS 471.025 |
| |