2005-03-30 00:00:00************* UNSAT 2ND REVIEW ******
  
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND PLEASE SEE NEW COMMENTS DUE
 TO COMPLETE CHANGE IN RISER DIAGRAM AND
 PANEL SCHEDULES.
  
 1)NOTE: PLEASE CORRELATEOCP /LOAD ETC
 FOR AHU'S. PLEASE SEE LOAD CALCULATIONS
 INDICATES A TOTAL OF 19KW, HOWEVER PANEL
 SCHEDULES INDICATE A TOTAL OF 13KW
  
 2)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS FOR EXISTING DWELLINGS.
 PLEASE SEE THE LOAD CALCULATIONS HAVE
 NOT BEEN CORRECTED.
  
 3)NOTE: PLEASE CORRELATE LOADS AND OCP
 SHOWN ON PANELS.
 PLEASE SEE MANY 1P20A CIRCUITS WITH LOAD
 EXCEEDING RATING OF CIRCUIT. A MAX OF
 1920VA ON 20A 1440VA ON 15A.
 PLEASE ALSO CORRELATE LOAD SHOWN FOR
 SUB-PANEL WITH LOAD ON PANEL "A".
 215.5
  
  
 4)NOTE: PLEASE CLARIFY LOCATION OF NEW
 125A DISC. IT IS NOTED FOR THIS NEW
 MAIN TO BE GARAGE. IS THIS GROUPED WITH
 EXISTING MCB PANEL? 230.72
 PLEASE SEE THIS HAS NOT BEEN ADDRESSED
 OR CLARIFIED.
  
 5)NOTE: PLEASE SEE 1/0'S ARE SHOWN FOR
 FEED TO 200A MCB PANEL.
 PLEASE SEE 310.16, 310.15B6, 240.4
  
 6)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR WHICH IS SHOWN FROM METER TO
 125A MAIN DISCONNECT. PLEASE SEE
 250.6,250.24, THIS EQUIPMENT GROUNDING
 IS ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISC.
  
 7)NOTE: PLEASE VERIFY IF LOADS SHOWN ON
 POOL PANEL FOR CONTINUOUS LOADS ARE AT
 125% MIN.
 215.3.230.42 ETC .
  
 8)NOTE: PLEASE SEE RANGE SHOWN AS 8KW
 AND DEMAND AT 1200VA? PLEASE ALSO SEE
 LOAD CALCS SHOWS 12KW??
  
 9)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES ARC FAULT FOR RECEPTS.
 PLEASE SEE 2002 210.12, WHICH IS NOT
 ONLY FOR RECEPTS.
  
  
 PLEASE SEE ONE SET OF THESE PLANS HAVE
 BEEN REDLINED FOR ABOVE AREAS OF NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  