Plan Review Notes
Plan Review Notes For Permit 04050095
Permit Number 04050095
Review Stop E
Sequence Number 3
Notes
Date Text
2005-01-31 00:00:00************* UNSAT ************
  
  
 PLEASE SEE PREVIOUS REDLINED ITEMS.
 PLEASE ALSO SEE NEW COMMENTS DUE TO
 COMPLETE REVISION OF SERVICE .
  
  
 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU'S. PLEASE ALSO SEE 2KW LOAD
 SHOWN ON A 15A CIRCUIT.
 MIN OCP 125%.
  
 2)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS FOR EXISTING DWELLINGS.
  
 3)NOTE: PLEASE CORRELATE LOADS AND OCP
 SHOWN ON PANELS.
  
 4)NOTE: PLEASE LABEL PANELS AND RISER
 FOR EACH PANEL.
  
 5)NOTE: PLEASE CLARIFY LOCATION OF NEW
 125A DISC. IT IS NOTED FOR THIS NEW
 MAIN
 TO BE GARAGE. IS THIS GROUPED WITH
 EXISTING MCB PANEL? 230.72
  
 6)NOTE: PLEASE SEE PANEL INDICATES A
 2-P25ABRKR FOR NEW SUB-PANEL, YET SUB
 PANELS INDICATES LOAD ABOVE 25A'S.
  
 7)NOTE: PLEASE VERIFY IF LOADS SHOWN ON
 POOL PANEL FOR CONTINUOUS LOADS ARE AT
 125% MIN.
 215.3.230.42 ETC .
  
 PLEASE SEE ONE SET OF THESE PLANS HAVE
 BEEN REDLINED FOR ABOVE AREAS OF
 CONCERN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 805-6717
 [email protected]
  
  