Plan Review Notes For Permit 04050095 |
Permit Number |
04050095 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-01-31 00:00:00 | ************* UNSAT ************ | | | | | | PLEASE SEE PREVIOUS REDLINED ITEMS. | | PLEASE ALSO SEE NEW COMMENTS DUE TO | | COMPLETE REVISION OF SERVICE . | | | | | | 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP | | FOR AHU'S. PLEASE ALSO SEE 2KW LOAD | | SHOWN ON A 15A CIRCUIT. | | MIN OCP 125%. | | | | 2)NOTE: PLEASE SEE 220.31B FOR LOAD | | CALCULATIONS FOR EXISTING DWELLINGS. | | | | 3)NOTE: PLEASE CORRELATE LOADS AND OCP | | SHOWN ON PANELS. | | | | 4)NOTE: PLEASE LABEL PANELS AND RISER | | FOR EACH PANEL. | | | | 5)NOTE: PLEASE CLARIFY LOCATION OF NEW | | 125A DISC. IT IS NOTED FOR THIS NEW | | MAIN | | TO BE GARAGE. IS THIS GROUPED WITH | | EXISTING MCB PANEL? 230.72 | | | | 6)NOTE: PLEASE SEE PANEL INDICATES A | | 2-P25ABRKR FOR NEW SUB-PANEL, YET SUB | | PANELS INDICATES LOAD ABOVE 25A'S. | | | | 7)NOTE: PLEASE VERIFY IF LOADS SHOWN ON | | POOL PANEL FOR CONTINUOUS LOADS ARE AT | | 125% MIN. | | 215.3.230.42 ETC . | | | | PLEASE SEE ONE SET OF THESE PLANS HAVE | | BEEN REDLINED FOR ABOVE AREAS OF | | CONCERN. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | 805-6717 | | [email protected] | | | | |
|