Plan Review Notes For Permit 04050095 |
Permit Number |
04050095 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-06-14 00:00:00 | *** NOTE REDLINED **** | | | | OCP FOR AHU, MIN 125% PER 424.3B MIN 30A | | | | ALL EXISTIN TO MEET FBC 34 SD'S AND GFI' | | S. | | | | SEC'S PER 310.16,240.4, 310.15B6, SHOWN | | AS 1/0'S |
|