2004-05-08 00:00:00 | ************** UNSAT ****************** |
| |
| 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| FOR NEW AND EXSITING LOADS FOR PANEL/ |
| SERVICE. 220/215.5 |
| PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 2)NOTE: PLEASE SEE RISER DIAGRAM FOR |
| SIZE OF CONDUCTORS SHOWN FOR NEW SUB |
| PANEL. (MISPRINT) SHOWS 6/0'S AND 10/0'S |
| FOR 60A PANEL. |
| |
| 3)NOTE: PLEASE SHOW GROUNDING SYSTEM AT |
| DETACHED BLDG PER 250.32, NEW FOOTER, |
| CWP (IF METALLIC). |
| |
| 4)NOTE: PLEASE INDICATE MEANS OF DISC |
| AT DETACHED BLDG. IS THIS GOING TO BE |
| A MCB IN NEW SUB PANEL. |
| |
| 5)NOTE: PLEASE SEE MISSING SD'S INSIDE |
| STUDY/ ADAPTABLE SLEEPING RM PER NFPA-72 |
| 8-1. |
| PLEASE ALSO NOTE, THESE WILL BE REQ'D |
| TO BE TIED INTO EXISTING/ NEW SD'S. |
| |
| 6)NOTE: PLEASE SEE FBC CHAPTER 34, |
| 3401.7.2.6 VALUE EXCEEDING 50% OF EXSIT |
| PLEASE PROVIDE LAYOUT OF EXISTING RES |
| MEETING 2002 NEC. IF EXIST MEETS 2002 |
| NEC, PLEASE SHOW AS. GFI/ARC FAULT, MIN |
| CIRCUITS, SD'S ETC. |
| |
| 7)NOTE:P PLEASE SEE PLANS, NEXT TO NEW |
| ADDITION, SHOWS NEW A/C UNIT, HOWEVER |
| NEW CABANA ALSO SHOWS A/C UNITS, ARE |
| THESE NEW OR EXSITING? |
| PLEASE VERIFY IF NEW A/C FOR ADDITION |
| IS FED FROM WHAT APPEARS TO BE NEW |
| CABANA PANEL? |
| |
| PLEASE ALSO VERIFY OCP SHOWN FOR 5KW |
| HEAT IN AHU. SHOWS 40A OCP. MIN. IS |
| 125% PER 424.3B , PLEASE VERIFY MAX. |
| |
| 8) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 9)NOTE: PLEASE SEE NOTE UNDER RISER |
| MENTIONS TO USE EXISTING CIRCUITS FOR |
| NEW??? |
| |
| 10)NOTE: PLEASE SHOW LOCATION OF NEW |
| PANEL. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| 11)NOTE: PLEASE VERIFY IF NEW |